B-8

NOTE 1.

The Entity concept allows interconnection of intrinsically safe apparatus to associated apparatus not specifically examined in combination as a system. The approved values of max. open circuit voltage (Uo) and max. short circuit current (Io) and max. power (Uo x Io / 4), for the associated apparatus must be less than or equal to the maximum safe input voltage (Ui), maximum safe input current (Ii), and maximum safe input power (Pi) of the intrinsically safe apparatus. In addition, the approved max. allowable connected capacitance (Co) of the associated apparatus must be greater than the sum of the interconnecting cable capacitance and the unprotected internal capacitance (Ci) of the intrinsically safe apparatus, and the the approved max. allowable connected inductance (Lo) of the associated apparatus must be greater than the sum of the interconnecting cable inductance and the unprotected internal inductance (Li) of the intrinsically safe apparatus.

INTRINSICALLY SAFE ENTITY PARAMETERS

GAS GROUP

Ui (Vmax)

Ii (Imax)

Ci

Li

Pi

A & B

30V

130 mA

0 nF

0 uH

1W

C

30V

130 mA

0 nF

0 uH

1W

D

30V

130 mA

0 nF

0 uH

1W

 

 

 

 

 

 

Note : The entity parameters listed above apply only to associated apparatus with linear output !

NOTE 2.

Installations in Canada shall be in accordance with the

Canadian Electric Code.

NOTE 3.

The positive power supply terminal shall be connected to the terminal designated "+SIG/COM" and the negative supply to the terminal designated "-SIG/COM".

EX-CERTIFIED PRODUCT. No modifications permitted without reference to the Ex-certifying Authorities.

APPROVALS/077-9451

ISSUE

CHANGE ORDER No

WEEK

ISSUE

CHANGE ORDER No

WEEK

ISSUE

CHANGE ORDER No

WEEK

1

SME-2918

0213

 

 

 

 

 

 

TRANSMITTER HEAD 3300 SERIES

Power Supply and output signal

NOTE 1.

NOTE 2.

NOTE 3.

 

ISSUED BY

WEEK

PRODUCT CODE

 

 

TITLE

 

 

9150077-945

GU-LN

0213

3300

 

 

SYSTEM CONTROL DRAWING

APPROVED BY

WEEK

DOC. TYPE

FILE

for hazardous location installation

GU-PO

0213

6

 

OrCAD

 

 

 

 

 

 

of CSA approved apparatus

 

ALL DIMENSIONS ARE IN MILLIMETRES.

FINISH, UNLESS

 

 

 

 

OTHERWISE STATED:

 

 

 

 

 

 

 

 

 

DWG NO.

ISSUE

SHEET

 

 

 

 

 

 

9150077-945

1

1 / 1

 

 

 

1 ST ANGLE

 

SCALE

The copyright/ownership of this document is and will remain ours.

 

 

 

 

 

 

1:1

The document must not be used without our authorization or brought

 

 

 

 

 

to the knowledge of a third party. Contravention will be prosecuted.

 

 

 

 

 

 

 

 

Saab Marine Electronics AB, Sweden

 

 

 

 

 

 

 

 

 

 

 

 

Figure B-6. System Control Drawing for hazardous location installation of CSA approved apparatus.

Rosemount 3300 Series

5HIHUHQFH￿0DQXDO 00809-0100-4811, Rev AA October 2002

Page 112
Image 112
Emerson Process Management rosemount 3300 series manual 9150077-945