Emerson Process Management rosemount 3300 series manual 6HWXS2XWSXW

Models: rosemount 3300 series

1 128
Download 128 pages 23.28 Kb
Page 61
Image 61

5HIHUHQFH￿0DQXDO￿

00809-0100-4811, Rev AA October 2002

Rosemount 3300 Series

6HWXS￿￿￿2XWSXW

The 2XWSXW tab lets you assign up to four transmitter variables

Figure 4-15. Setup output tab

 

 

RCT-SETUP_OUTPUT

 

Typically, the 3ULPDU\￿9DULDEOH (PV) is configured to be Product Level,

 

Interface Level or Volume.

 

Other variables like Product Distance, Interface Distance, Upper Product

 

Thickness, etc. are available as well.

 

For model 3301 the primary variable is typically set to be Level. If the

 

transmitter is in the Immersed Probe mode (see section

 

“Measurement Mode” ) the PV is normally set to Interface Level.

 

For the model 3302 the PV is typically set to Interface Level, but Level and

 

other options may also be used.

 

Set the /RZHU￿5DQJH￿9DOXH (4 mA) and the 8SSHU￿5DQJH￿9DOXH (20 mA) to

 

the desired values. Keep in mind that the 20 mA value should be below the

 

Upper Dead Zone, and the 4 mA point should be above the Lower Dead Zone

 

if you want to use the full 4-20 mA range within the measuring range of the

 

transmitter.

 

Also make sure that the 20 mA value is set below the Upper Null Zone (UNZ).

 

(the UNZ parameter may be used if there are measurement problems in the

 

upper part of the tank, see 6HFWLRQ￿￿￿￿'LVWXUEDQFHV￿DW￿WKH￿WRS￿RI￿WKH￿WDQN). The

 

UNZ is equal to zero in the default configuration.

 

See 6HFWLRQ￿￿￿￿'HDG￿=RQHV for more information on Upper and Lower Dead

 

Zones.

 

See 6HFWLRQ￿￿￿￿%DVLF￿&RQILJXUDWLRQ for more information on setting the Upper

 

and Lower Range values.

 

The default 'DPSLQJ value is 10. Normally this value does not need to be

 

changed. The Damping parameter may be changed if there are high filling

 

rates, see “High Level Rates” on page 6-7for more information.

4-19

Page 61
Image 61
Emerson Process Management rosemount 3300 series manual 6HWXS2XWSXW