Rosemount 3300 Series

',$*1267,&￿ 0(66$*(6

7URXEOHVKRRWLQJ

If there is a malfunction despite the absence of diagnostic messages, see

 

 

Table 6-1for information on possible causes.

 

Table 6-1. Troubleshooting

 

 

 

 

 

chart

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No HART communication.

 

• COM Port configuration does not match

• Check that correct COM Port is

 

 

 

 

the connected COM Port.

 

selected in the HART server (see

 

 

 

Cables may be disconnected.

 

“Specifying the COM Port” on

 

 

 

• Wrong HART adderss is used.

 

page 4-14.

 

 

 

Hardwafe failure.

Check wiring diagram.

 

 

 

 

 

Verify that the 250 Ohm resistor is in

 

 

 

 

 

 

the loop.

 

 

 

 

 

Check cables.

 

 

 

 

 

Make sure that correct HART short

 

 

 

 

 

 

address is used. Try address=0.

 

 

 

 

 

Check Analog Output current value to

 

 

 

 

 

 

verify that transmitter hardware works.

 

 

 

 

 

 

 

Analog Out is set in Alarm.

 

 

 

Use the command “Read Gauge Status”

 

 

 

 

 

in order to check active errors.

 

 

 

 

 

Both P2 and P3 are detected but Interface

Measurement Mode is set to “Level Only”.

Set Measurement Mode to “Level and

 

Level is reported as Not A Number (NAN)

 

 

Interface” (see “Basic Configuration” on

 

in the waveform plot.

 

 

 

page 4-9).

 

 

 

 

 

 

Both Level and Interface Level are

 

Probe is not connected.

Use the command “Read Gauge Status”

 

reported as NAN.

 

 

 

and check if error “Probe Failure” is

 

 

 

 

 

active. If this is the case, check the probe

 

 

 

 

 

connection.

 

 

 

 

 

 

Both P2 and P3 are detected but the

P3 is identified as a double bounce.

Adjust thresholds T2 and T3, see

 

interface level is equal to the product

P2 and P3 are very close.

“Amplitude Threshold Settings” on

 

Level.

 

 

 

page 6-13for more information.

 

 

 

 

 

 

P2 is detected but Level is incorrectly

 

 

Use the command “Read Gauge Status”

 

reported as Full or Empty.

 

 

 

and check if the warning “Probe

 

 

 

 

 

Immersed” is active. If this is the case

 

 

 

 

 

check that:

 

 

 

 

 

the transmitter is configured with

 

 

 

 

 

 

correct probe type,

 

 

 

 

 

the reference pulse (P1) is below

 

 

 

 

 

 

amplitude threshold T4. If not, adjust

 

 

 

 

 

 

T4 to an appropriate value.

 

 

 

 

 

 

 

The reference pulse is not detected.

The tank is full.

Check the product level.

 

 

 

The transmitter is configured with

Check that correct probe type is

 

 

 

 

wrong probe type.

 

configured.

 

 

 

Amplitude Threshold T1 is not correct.

Check Amplitude Threshold T1.

 

 

 

 

 

 

 

 

Level accuracy seems off.

 

Configuration error.

Check the Reference Gauge Height

 

 

 

 

 

 

parameter.

 

 

 

 

 

Check status information and

 

 

 

 

 

 

diagnostic information.

 

 

 

 

 

 

 

 

Integral display does not work.

 

 

 

Check the display configuration.

 

 

 

 

 

Check loop power.

 

 

 

 

 

Check Display connection.

 

 

 

 

 

 

 

6-19