Rosemount 3300 Series

5HIHUHQFH￿0DQXDO

00809-0100-4811, Rev AA October 2002

(UURUV￿

Table 6-2 is a list of diagnostic messages that may be displayed on the

 

 

Integral Display, on the Model 275 HART Communicator, in AMS or by the

 

 

Radar Configuration Tools (RCT) software. Errors normally result in Analog

 

Output alarm.

 

 

Errors are indicated in RCT by the message “Transmitter malfunction”:

 

 

 

 

￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿￿

TRANSMITTERMALFUNCTION

 

 

 

To see the error message do one of the following:

• Click the Read Gauge Status icon

in the toolbar at the top of the

RCT workspace.

 

1. Open the Advanced section in the RCT workspace Project Bar and click the Device Commands icon,

or

choose the Device Commands option from the View menu.

2. Open the folder named Diag and double-click the Read Gauge Status option.

Table 6-2. Error messages.

 

 

 

 

Invalid configuration.

At least one configuration parameter

Load default database and restart

 

is outside allowed range.

 

the transmitter.

 

NOTE: the default values are used

• Contact Saab Rosemount service

 

until the problem is solved.

 

department if the problem persists.

 

 

 

RAM failure was

The transmitter performs an

Contact Rosemount service

detected during

immediate reset.

department.

startup test.

 

 

 

 

 

 

FPROM failure was

The transmitter performs an

Contact Rosemount service

detected during

immediate reset.

department.

startup test.

 

 

 

 

 

 

Waveform acquisition

This error is probably caused by

Contact Rosemount service

failure.

hardware failure.

department.

 

 

 

EEPROM factory

Checksum error in the factory

Contact Rosemount service

checksum.

configuration parameters. Can be

department.

 

caused by power failure during

 

 

 

configuration or by hardware error.

 

 

 

NOTE: the default values are used

 

 

 

until the problem is solved.

 

 

 

 

 

 

EEprom user

Caused by error in the User

Load default database and restart

checksum error.

Configuration parameters. Can be

 

the transmitter.

 

caused by power failure during

Contact Saab Rosemount service

 

configuration or by hardware error.

 

department if the problem persists.

 

NOTE: the default values are used

 

 

 

until the problem is solved

 

 

 

 

 

Software error.

 

Contact Rosemount service

 

 

department.

 

 

 

Probe failure.

Probe is not detected.

Check that the probe is correctly

 

 

mounted.

 

 

 

 

6-20

Page 90
Image 90
Emerson Process Management rosemount 3300 series manual Uuruv