Figure 3-1. Switches for Alarm

and Write Protection

6￿￿￿￿￿￿￿￿￿￿￿￿￿￿

 

￿￿￿￿￿￿)￿￿￿￿￿

SWITCH WRP ALARM

To set the Alarm and Write Protect switches do the following:

1.Remove the cover on the circuit side (see main label).

2.To set the 4-20 mA alarm output to Low, move the Alarm switch to the LOW position. HIGH is the factory default setting (see Figure 3-1).

3.To enable the security write protection feature, move the Write Protect switch to the ON position. The OFF position is the factory default setting (see Figure 3-1).

4.Replace and tighten the cover.

3-5