Emerson Process Management rosemount 3300 series manual Wudqvplwwhurqwkhexv, Multidrop connection

Models: rosemount 3300 series

1 128
Download 128 pages 23.28 Kb
Page 41
Image 41

5HIHUHQFH￿0DQXDO￿

00809-0100-4811, Rev AA October 2002

Rosemount 3300 Series

8VLQJ￿0RUH￿WKDQ￿RQH￿

WUDQVPLWWHU￿RQ￿WKH￿EXV

The 3300 transmitter can be run in multidrop mode. In the multidrop mode each transmitter has a unique HART address.

Figure 3-15. Multidrop connection

MULTIDROP

The poll address can be changed by using a HART 275 Communicator or by using the Rosemount Configuration Tools software.

To change the poll address using a 275 Communicator choose HART command [1, 4, 5, 2, 1].

To change the poll address using the Rosemount Configuration Tools (RCT) software do the following:

1.Choose the View>Device Commands option. or

choose the Device Commands icon from the Project Bar Advanced section.

RCT_DEVICECOMMANDS_POLLADDRESS.TIF

2.Open the Details folder.

3.Choose the Set Poll Address option.

4.Set the desired address.

3-21

Page 41
Image 41
Emerson Process Management rosemount 3300 series manual Wudqvplwwhurqwkhexv, Multidrop connection