3

Program Folders in Logicmaster 90

With the Logicmaster programming software, there must be different folders for each configuration. If the logic is identical for both PLCs, a third folder could be used for the logic and reference tables. This results in three folders for the system.

Folder A - configuration for the Primary unit.

Folder B - configuration for the Secondary unit.

Folder C - logic and reference tables for both systems.

CPU Configuration Parameters

When configuring a system for Hot Standby CPU Redundancy, the following additional parameters must be set up.

Parameter

Default

Choices

Description / Comment

 

 

 

 

I/O Scan Stop

Must be set to NO

 

 

 

 

 

Watchdog

200ms

10ms to

The value selected should allow for the expected

Timer

 

1000ms

scan plus two fail wait times.

 

 

 

 

Redund

Primary

Primary,

Whether the CPU being configured is the Primary or

Type

 

Secondary

Secondary CPU in the Redundancy system. One

 

 

 

configuration must be set to Primary; the other to

 

 

 

Secondary.

 

 

 

 

Background

5ms in limited

0ms to

The background window runs several diagnostic tests

Timer

window mode

255ms

that can be disabled by setting the timer to 0ms.

 

 

 

These tests are run in Constant Window and

 

 

 

Constant Sweep mode only if the window/sweep

 

 

 

time is large enough.

 

 

 

 

Fail-wait

60ms

60ms to

The time one PLC will wait on one Redundancy

 

 

400ms

Communications Module link for the other PLC to

 

 

 

respond before faulting that link. The CPU will try

 

 

 

both links before continuing its scan. Once the RCM

 

 

 

links are marked as failed, one unit or the other must

 

 

 

be power cycled to recover them.

 

 

 

Storing configuration to either unit could also

 

 

 

recover the RCM links.

 

 

 

 

Control

GHS (CPU780)

GHS or

Genius Hot Standby (GHS) or

Strategy

GDB (CGR772,

GDB

Genius Dual Bus (GDB).

 

CGR935)

 

 

 

 

 

 

Shared I/O

The references within the control of the Redundancy system. See the following

References

paragraphs for more information. The Shared I/O selections must match exactly

 

between Primary and Secondary PLCs.

 

 

 

 

Fault

 

Fatal,

Fault actions when the CPUs are not synchronized

Category

 

Diagnostic

can be configured to select a safe shutdown or fault

(configurable

 

 

tolerant operation in case a failure occurs with no

when not

 

 

backup ready.

synchronized

 

 

 

only)

 

 

 

 

 

 

 

3-2

Series 90™-70 Enhanced Hot Standby CPU Redundancy User's Guide – May 2000

GFK-1527A

Page 35
Image 35
GE 90-70 manual CPU Configuration Parameters, Program Folders in Logicmaster