GFK-1527A Chapter 4 Normal Operation 4-17
4
Example 5: Role switches allowed on both units Seco ndary Unit Active
Note: Secondary unit active is not a recommended mode of opera ti on when using the GHS
Control Strategy.
Primary Unit Secondary Unit
Role Backup Active
Operating Mode RUN/ENABLED RUN/ENABLED
OK LED on RCM ON ON
LOC_RDY LED on RCM and %S Bit ON ON
LOC_ACT LED on RCM and %S Bit OFF ON
REM_RDY LED on RCM and %S Bit ON ON
REM_ACT LED on RCM and %S Bit ON OFF
Example 6: Role switches not a llowed on either unit, Secondar y UnitActive
Note: Secondary unit active is not a recommended mode of opera ti on when using the GHS
Control Strategy.
Primary Unit Secondary Unit
Role Backup Active
Operating Mode RUN/DISABLED RUN/ENABLED
OK LED on RCM ON ON
LOC_RDY LED on RCM and %S Bit OFF ON
LOC_ACT LED on RCM and %S Bit OFF ON
REM_RDY LED on RCM and %S Bit ON OFF
REM_ACT LED on RCM and %S Bit ON OFF
Example 7: Role switches allowed on both unit s, Secondary Unit Active
Note: Secondary unit active is not a recommended mode of opera ti on when using the GHS
Control Strategy.
Primary Unit Secondary Unit
Role Backup Active
Operating Mode RUN/DISABLED RUN/DISABLED
OK LED on RCM ON ON
LOC_RDY LED on RCM and %S Bit OFF OFF
LOC_ACT LED on RCM and %S Bit OFF ON
REM_RDY LED on RCM and %S Bit OFF OFF
REM_ACT LED on RCM and %S Bit ON OFF