5

PLC Fault Table Messages for Redundancy

The following table lists messages, descriptions, and corrective actions for error codes associated with the redundancy fault group. These error codes can be viewed by selecting Ctrl-F on the corresponding redundancy fault (in Logicmaster 90-70) or double-click on the corresponding fault (in Control). The entire fault data (including these error codes) can also be accessed with a SVC_REQ and other applications that communicate with the CPU.

Error

 

 

 

Code

Message

Fault Description

Corrective Action

1

Primary Unit is Active and

The primary and secondary units have

None required.

 

Secondary Unit is Backup.

switched roles.

 

2

Secondary Unit is Active

The secondary and primary units have

None required.

 

and Primary Unit is

switched roles.

 

 

Backup.

 

 

3

Primary Unit is Active; No

The primary unit has transitioned to RUN

Secondary unit MUST be placed in RUN

 

Backup Unit Available.

mode and is running as a stand-alone unit.

mode with a comparable configuration in

 

 

 

order to have a synchronized system.

 

 

 

 

4

Secondary Unit is Active;

The secondary unit has transitioned to RUN

Primary unit MUST be placed in RUN

 

No Backup Unit Available.

mode and is running as a stand-alone unit.

mode with a comparable configuration in

 

 

 

order to have a synchronized system.

5

Primary Unit Has Failed;

Primary unit has recorded a fatal fault, has

If primary unit has also logged the fault

 

Secondary Unit is Active

been powered down, or has lost ability to

“Secondary Unit Has Failed: Primary Unit

 

w/o Backup.

communicate with the secondary unit while

is Active w/o Backup”, then

 

 

acting as the active or backup unit.

communications has been broken between

 

 

Secondary unit will continue running as a

the two units and must be repaired. If a

 

 

stand-alone unit.

fatal fault has been logged in the primary

 

 

 

unit, the indicated fault must be repaired.

 

 

 

Power may have to be cycled on one of the

 

 

 

units in order to re-establish

 

 

 

communications and return to a

 

 

 

synchronized system.

6

Secondary Unit Has Failed;

Secondary unit has recorded a fatal fault, has

If secondary unit has also logged the fault

 

Primary Unit is Active w/o

been powered down, or has lost ability to

“Primary Unit Has Failed: Secondary Unit

 

Backup.

communicate with the primary unit while

is Active w/o Backup”, then

 

 

acting as the active or backup unit. The

communications has been broken between

 

 

primary unit will continue running as a

the two units and must be repaired. If a

 

 

stand-alone unit.

fatal fault has been logged in the secondary

 

 

 

unit, the indicated fault must be repaired.

 

 

 

Power may have to be cycled on one of the

 

 

 

units in order to re-establish

 

 

 

communications and return to a

 

 

 

synchronized system.

7

Synchronization Failure;

A communications failure between the two

One of the units should be power cycled to

 

Both Units are Active.

units has caused each unit to become stand-

return to a synchronized system. NOTE:

 

 

alone units. Communications has since been

The Genius blocks will respond to the unit

 

 

restored.

that is using Serial Bus Address 31.

8

Unable to Switch

An attempt to switch redundancy roles was

None required.

 

Redundancy Roles

made when it was not possible to perform

 

 

 

the switch.

 

GFK-1527A

Chapter 5 Fault Detection

5-3

Page 67
Image 67
GE 90-70 manual PLC Fault Table Messages for Redundancy, Message Fault Description Corrective Action