5-40 Field Control Genius® Bus Interface Unit User’s Manual October 1999 GFK-0825F
5
Configure a 16-Point Grouped Analog Input Module
When you select “Read” fr om the empty slot HHM screen, thi s module screen appears:

S:4 ALG240 1.0

< > del zoom
Assign I/O References for the Module
When you "zoom" into the mod u l e's slot, a screen like this ap p ear s:
Default data length

S:4 AI *AI:016

AI01307-01322

< > chg entr

Default BIU data type Next available reference
This screen shows the default table and length, and the next available reference address in
that table for that reference parameter. The length is displayed in units that are
appropriate for that da ta type (AI and AQ are in words, Q and I are in bits). The asterisk
indicates that this r efer ence has not yet been defin ed .
If the present selection is acceptable, press F4 (en t er) to accept it. The asterisk wil l
disappear. If you prefer t o change the BIU table mapping, l ength, or reference value, pr es s
F3 (change).
S:4 AI AI
Select table

tgl entr

From this screen, you can display the other BIU data types by pressing F3 (toggle). Press
F4 (enter) when the desired data type is displayed.

S:4 AI AI:016

Select length

clr entr

If you want to enter a different length for the displayed data type, press F3 (clear) to clear
the length field. Ent er th e n ew l en gth from the keypad. If you ent er an in valid length, the
HHM prompts: BAD LENGTH ERR
S1 FILTERING
20MS
S1 LINE FREQ
60 HZ
S1: Q *Q016
Q00001-00016
S1 Module-> %I
DEFAULT ZERO
S1: I * I:088
I00001-00088
S1 Module-> %AI
DEFAULT ZERO
S1: ALG240: 1.1
F4
S1: AI *AI016
AI00001-00016
F4, F2
F4, F2
F4, F2
F2 F1
S1 Network->%Q
DEFAULT ZERO
F2 F1
F2 F1
F2 F1
F1
F2
S1 CH 1
ACTIVE
S1 CH1 DEF RNG
1
S1 CH1 SPAN L
04000
S1 CH1 ENG L
04000
S1 CH1 ENG H
20000
S1 CH1 AL H
20000
S1 CH1 SPAN H
20000
S1 CH1 AL L
04000
F1, F2 select
channels
F2 F1
F2 F1
F2 F1
F2 F1
F2 F1
F2 F1
F2 F1
F2 F1
Re
p
eat for other
channels
F2
S1 CH 1
CONFIG
F4 ZOOM
S1 LINE FREQ
60 HZ
F1