GFK-0825F Chapter 5 Station Configuration 5-11
5
Configure Genius Bus Redundancy
If the Bus Interface Unit will be used as a bus switching device itself, or located on a bus stub
downstream of another device that acts as a bus switching device, BSM Present should be set to
YES. For all other applications, set it to NO.
BSM Present
NO
< > tgl entr
1. If you want to go to the next screen without making a change, press F2 ( > ).
If the selecti on should be ch anged, press F3 (tgl).
2. Press F4 (entr).
If you selected NO, go to the next page.
If you selected YES, th e follo wi n g screen appears:
BSM Controller
NO
< > tgl entr
3. If the Bus Interface Unit will be used as the bus switching device itself, set BSM Controller to
YES. For all other applications, set it to NO.
Next, the Output Default Time screen appears:
Out Def Time
2.5 sec
< > tgl entr
4. If the total bus scan time i s exp ect ed to exceed 100mS, set the Output Default Time to 10
seconds. The Output Default Time is normally 2.5 seconds. If the Bus Interface Unit stops
receiving outputs fr om th e Bu s C ontroller, it will wait for th i s specified time period befor e
defaulting outputs in the station.
If you want to go to the next screen without making a change, pr es s F 2 ( > ).
If the selecti on should be ch anged, press F3 (tgl).
5. Press F4 (entr).