Example 2: Discrete and Analog Data, Network Processing
In this I/O Station, there are both discrete and analog I/O modules. All data is included within the
I/O map that is configured for the Bus Interface Module, an d exchanged over the network. There is
no local Micro Field Process or.
BIU Map: I00001 - I00112
Q00001 - Q00040
AI00001 - AI00024
AQ00001 - AQ00004
No synch ronization is required.
Slot 1: 12VDC 16-Point Pos/Neg Input Module
(IC670MDL640) I00001 - I00016
Slot 2: 120VAC 8-Point Isolated Input Module (IC670MDL242) I00017 - I00024
Slot 3: 5/12/24VDC 16-Point Output Module (IC670MDL742) Q00001 - Q00016
Slot 4: 8-Point Relay Output Module (IC670MDL930) Q00017 - Q00024
Slot 5: 8-Channel Analog Input Module (IC670ALG230) AI00001 - AI00008
Slot 6: High-level 16-Channel Analog Input Module
(IC670ALG240):
analog inputs:
diagnostic inputs:
control outputs:
AI00009 - AI00024
I00025 - I00112
Q00025 - Q00040
Slot 7: 4-Channel Analog Output Module (IC670ALG320) AQ00001 - AQ00004