Operating instructions

 

 

 

 

 

Troubleshooting guide

 

 

 

 

 

Problem

 

Cause

 

Remedy

 

 

 

 

 

 

 

Position control not always working

 

Potentiometer ranges shifted

 

New calibration with Opus

 

 

 

Actuator for angle sensor out of

 

Readjust and recalibrate angle sensor

 

 

 

adjustment

 

 

 

 

 

 

 

 

Directional control valve leaky

 

Foreign particles in seat valve

 

Remove, clean or replace valve

 

 

 

 

 

cartridge

 

 

 

 

 

No pressure build-up

 

Slide valve in input plate stuck

 

Remove, clean slide valve or replace

 

 

 

(foreign particles)

 

plate

 

 

 

 

 

Strong oil flow fluctuation in flow

 

Lack of oil

 

Higher RPM, reduce demand of 2nd

divider I or oil flow too low

 

 

 

load

 

 

 

 

 

 

 

Troubleshooting is also possible with Opus or the PC soft- ware in the menu

Keyboard Check: Keyboard buttons.

Output functions XO...Y3: Check if box provides current for valves.

Rear power lift position limiter: Functions of lift posi- tion control.

Cushioning device: Functions of hydraulic implement cushioning

Desired value channel.

FCE1: Joystick functions.

Diagnosis of master inputs.

Diagnosis of BKN nodes.

Use the circuit diagrams and wiring diagrams.

Also refer to the Bucher Hydraulics operating instructions.