DCP200 Profile Controller & Recorder -Product Manual
Page 106 Modbus Parameters 51-52-25-150, Issue 1 April 2009
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Alarm 5 Type 6208 0x1840 R/W
Value
Alarm 5 Type
0Process High Alarm
1Process Low Alarm
2Deviation Alarm (SP-PV)
3Band Alarm
4Loop Alarm
5Input/Sensor Break Alarm
6Auxiliary Input A Break Alarm
7Auxiliary Input B Break Alarm
Alarm 5 Value 6209 0x1841 R/W Limited by the input range maximum and minimum for
Alarm types 0 and 1. Limited by the input span for
alarm types 2 and 3. Not used for alarms 4 to 7.
Alarm 5 Hysteresis 6210 0x1842 R/W Limited by the input span
Alarm 5 Inhibit
Enable/disable
6211 0x1843 R/W
Value
Alarm 5 Inhibit Enable
0Disabled
1Enabled
Alarm 5 Status 6212 0x1844 RO
Value
Alarm 5 Status
0Inactive
1 Active
Alarm 5 Inhibit
Status
6213 0x1845 RO
Value
Alarm 5 Inhibit Status
0Not Inhibited
1Inhibited
Recorder & Clock Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Recording Sample
Interval
7550 0x1D7E R/W
Value
Recording Sample Interval
0Every Second
1Every 2 Seconds
2Every 5 Seconds
3Every 10 Seconds
4Every 15 Seconds
5Every 30 Seconds
6Every Minute
7Every 2 Minutes
8Every 5 Minutes
9Every 10 Minutes
10 Every 15 Minutes
11 Every 30 Minutes
Recording Mode 7551 0x1D7F R/W
Value
Recording Mode
0Record until memory used
1Continuous FIFO buffer
Start Stop
Recording
7552 0x1D80 R/W
Value
Operator Start
/Stop Recording
0Stop Recording