DCP200 Profile Controller & Recorder -Product Manual
Page 182 Specifications 51-52-25-150, Issue 1 April 2009
Conditions For Use

Reference Test Conditions

Ambient Temperature: 20C ±2C.
Relative Humidity: 60 to 70%.
Supply Voltage: 100 to 240V AC 50Hz ±1%.
Source Resistance: <10Ω for thermocouple input.
RTD Lead Resistance: <0.1Ω/lead balanced (Pt100).

Operating Conditions

Ambient Temperatures 0C to 55C (operating) and -20C to 80C (storage).
Relative Humidity: 20% to 95% non-condensing.
Altitude: Up to 2000m above sea level.
Supply Voltage: Either 100 to 240V ±10% AC 50/60Hz
or 20 to 48V AC 50/60Hz & 22 to 55V DC for low voltage versions.
Power Consumption: Mains versions: 24VA.
Low voltage versions: 15VA / 12W.
Source Resistance: 1000Ω maximum (thermocouple).
RTD Input Lead
Resistance:
50Ω per lead maximum, balanced
Standards
Conformance Norms: CE, UL, ULC.
EMC standards: Complies with CE EN61326.
Safety Standards: Complies with CE EN61010-1 and UL3121.
Pollution Degree 2, Installation Category II.
Front Panel Sealing: To IP66 (IP65 front USB connector). IP20 behind the panel.
(IP ratings are not tested for or approved by UL)
Dimensions
Front Bezel Size: 1/4DIN (96 x 96mm).
Mounting: Plug-in with panel mounting fixing strap.
Panel Cut-out Size: 92mm x 92mm. Max panel thickness 6.0mm
Depth Behind Panel: 117mm
Ventilation 20mm gap required above, below and behind.
Weight: 0.65kg maximum.
Terminals: Screw type (combination head).