DCP200 Profile Controller & Recorder -Product Manual
Page 52 Configuration & Use 51-52-25-150, Issue 1 April 2009
Setpoint Ramp Rate The Setpoint Ramp Rate value (1 to 9999 display units per hour or
OFF). This ramp is applied at power-up and any setpoint changes.
Local Setpoint 1 Value wSets the value of Local Setpoint 1 between the Setpoint Upper and
Lower Limits.
Local Setpoint 1 Offset A value added to the Setpoint 1 value (+ve values) or subtracted
from it (-ve values). Use when the instrument is a slave in multi-zone
applications to achieve a zone offset. Otherwise, always set to zero.
Local Setpoint 2 Value wSets the value of Local Setpoint 1 between the Setpoint Upper and
Lower Limits.
Local Setpoint 2 Offset A value added to the Setpoint 2 value (+ve values) or subtracted
from it (-ve values). Use when the instrument is a slave in multi-zone
applications to achieve a zone offset. Otherwise, always set to zero.
Output Configuration Sub-Menu

Table 11. Output Configuration Sub-Menu Screens

Outputs Configuration

:

No Outputs Warning Shown if the Outputs Configuration menu is entered on an
instrument without any output modules fitted.
Linear Output nType wSet the desired type for any Linear Outputs fitted. From: 0-5, 0-10,
1-5, 2-10V & 0-20, 4-20mA or 0-10VDC adjustable Transmitter PSU.
Adjustable 0-10V
Transmitter PSU n
wSets the voltage required if Linear Output ntype is 0-10VDC
adjustable Transmitter PSU.
Output nUsage wSets the use for each output fitted. From: Primary or Secondary
Control; Alarms; Profile Events & Alarms; Retransmit Process
Variable or Setpoint. Choices offered are as appropriate for the
output type fitted (e.g. only Linear Outputs can retransmit).
Output nAlarm
Selection wWhen an Output Usage is Alarms, this selects which alarm(s) will
cause it to change state. From Alarm 1; 2; 3; 4; 5 or a Logical OR of
alarms 1 to 2; 1 to 3; 1 to 4 or 1 to 5. Each choice is selectable with
Direct Action (on during alarm) or Reverse Action (off during alarm).
Output nEvents wWhen an Output Usage is Events & Alarms, this selects which
Events(s) will cause it to change state. From: Profile Running or
Profile End; Event 1; 2; 3; 4; 5 or a Logical AND of Event n& Alarm
n. Each choice is selectable with Direct Action (on during event) or
Reverse Action (off during event). -Profiler version only
Retransmit Output n
Scale Low wSets the displayed value at which a retransmission output should be
at it’s minimum level (e.g. the display value when a 4 to 20mA PV
Retransmission output will be 4mA. Adjustable from -1999 to 9999.
Retransmit Output n
Scale High wSets the displayed value at which a retransmission output will be at
it’s maximum level (e.g. the display value when a 4 to 20mA PV
Retransmission output will be 20mA. Adjustable from -1999 to 9999.