DCP200 Profile Controller & Recorder -Product Manual
Page 102 Modbus Parameters 51-52-25-150, Issue 1 –April 2009
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Auxiliary Input B
Offset
4080 0x0FF0 R/W Setpoint is always limited within Setpoint Maximum
and Minimum
Auxiliary Input B
Value
4081 0x0FF1 RO The value of analogue Auxiliary Input B
User Setpoint Select 4122 0x101A R/W
Value
Setpoint Select
0Local Setpoint 1
1Alternate setpoint
Setpoint Ramp Rate 4123 0x101B R/W 0 to 10000 0 or >10000 = Off
Target Setpoint 4125 0x101D RO The target setpoint value when ramping
Operator Access To
Setpoint Ramp Rate
4126 0x101E R/W
Value
Operator Access To Ramp Rate
0Disabled
1Enabled
Selected Setpoint 4127 0x101F RO
Value
Selected Setpoint
0Local Setpoint 1
1Alternate setpoint
Actual Setpoint 8256 0x2040 RO The current instantaneous value of the active setpoint
Control ParametersParameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Manual Control
Select Method
4299 0x10CB R/W
Value
Manual Control Selection Meth
od
0Automatic Control Only
1Manual Control Only
2User Selectable From Key Pad
3Digital input A
4Digital input B
Control Enable
Select Method
4300 0x10CC R/W
Value
Control Enable Selection Method
0Enabled Only
1Disabled Only
2User Selectable From Key Pad
3Digital input A
4Digital input B
Primary Cycle Time 4301 0x10CD R/W 0.5 to 512.0 Seconds
Secondary Cycle
Time
4302 0x10CE R/W 0.5 to 512.0 Seconds
Control type 4310 0x10D6 R/W
Value
Control Typ
e
0Single Control
1Dual Control
Control Action 4311 0x10D7 R/W
Value
Control Type
0Direct Acting
1Reverse Acting
Primary Proportional
Band
4312 0x10D8 R/W 0.0 to 999.9 (% of Input Span)
Secondary 4313 0x10D9 R/W 0.0 to 999.9 (% of Input Span)