DCP200 Profile Controller & Recorder -Product Manual
51-52-25-150, Issue 1 April 2009 Modbus Parameters Page 85
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Input Signal Under
Range Flag
1033 0x0409 RO
Value
Process Input Under Range Status
0Inactive
1Active
Input Signal Over
Range Flag
1034 0x040A RO
Value
Process Input Over Range Status
0Inactive
1Active
Cold Junction
Compensation
Enable/disable
1035 0x040B R/W
Value
CJC Status
0Disabled
1
Enabled (
default
)
Calibration Reminder
Enable
1048 0x0418 R/W
Value
Calibration Reminder Status
0Disabled
1Enabled
Calibration Reminder
Date
1049 0x0419 R/W Data Format = ddmmyy where dd = day, mm = month
and yy = year (e.g. 200308 is 20th March 2008)
Calibration Reminder
Status
1052 0x041C RO
Value
Calibration Status
0Calibration OK
1Calibration Required
Multi-point Scaling
Enable
1053 0x041D R/W
Value
Multi
-
point Scaling Status
0Disabled
1
Enabled (
only if the input type is linear
)
Scale Point 1 1054 0x041E R/W 0.1 to 100.0%
Display Point 1 1055 0x041F R/W Valid between scale range maximum and minimum
Scale Point 2 1056 0x0420 R/W >Scale point 1 to 100.0%
Display Point 2 1057 0x0421 R/W Valid between scale range maximum and minimum
Scale Point 3 1058 0x0422 R/W >Scale point 2 to 100.0%
Display Point 3 1059 0x0423 R/W Valid between scale range maximum and minimum
Scale Point 4 1060 0x0424 R/W >Scale point 3 to 100.0%
Display Point 4 1061 0x0425 R/W Valid between scale range maximum and minimum
Scale Point 5 1062 0x0426 R/W >Scale point 4 to 100.0%
Display Point 5 1063 0x0427 R/W Valid between scale range maximum and minimum
Scale Point 6 1064 0x0428 R/W >Scale point 5 to 100.0%
Display Point 6 1065 0x0429 R/W Valid between scale range maximum and minimum
Scale Point 7 1066 0x042A R/W >Scale point 6 to 100.0%
Display Point 7 1067 0x042B R/W Valid between scale range maximum and minimum
Scale Point 8 1068 0x042C R/W >Scale point 7 to 100.0%
Display Point 8 1069 0x042D R/W Valid between scale range maximum and minimum
Scale Point 9 1070 0x042E R/W >Scale point 8 to 100.0%
Display Point 9 1071 0x042F R/W Valid between scale range maximum and minimum
Scale Point 10 1072 0x0430 R/W >Scale point 9 to 100.0%
Display Point 10 1073 0x0431 R/W Valid between scale range maximum and minimum
Scale Point 11 1074 0x0432 R/W >Scale point 10 to 100.0%
Display Point 11 1075 0x0433 R/W Valid between scale range maximum andminimum
Scale Point 12 1076 0x0434 R/W >Scale point 11 to 100.0%
Display Point 12 1077 0x0435 R/W Valid between scale range maximum and minimum