DCP200 Profile Controller & Recorder -Product Manual
51-52-25-150, Issue 1 April 2009 Profiler Option Page 69
Loops Segments
A Loop Segment goes back to a specified segment in the current profile. This action is
repeated for the required number of times (1 to 9999) before the profile continues onwards.
More than one Loop Segment can be used in a profile, but they must not cross.
Loop back target segment
End
Loop Segment
Figure 39. Loops Segments
Profile Running / Holding vs. Hold Segments
Hold Start
Run
Continue
Triggers
End
Hold Stop
Hold Segments
Figure 40. Run/Hold & Hold Segments
A Hold during a segment maintains the current setpoint value. Once the hold condition is
stopped the Ramp or Dwell continues. Depending on the configuration, a hold can be the
started & stopped by via a key-press, breaking the signal to a Run/Hold digital input, a serial
comms command or by the Auto-Hold feature (see below).
Note:
A running profile will also hold while Manual Control is selected.
A Hold Segment is a pre-planned hold, programmed into the profile. It maintains the value of
the previous segment. The profile does not continue until a Continue Trigger occurs. This
can be via a key-press, a digital input signal or after waiting for a time of day (available on
Recorder version only).
x 500
Example:
Runs segments 1 to 5, then
repeats segments 3 to 5 for 500
times, before continuing on to
segments 7 to 9,