DCP200 Profile Controller & Recorder -Product Manual
51-52-25-150, Issue 1 April 2009 Modbus Parameters Page 109
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Real Time Clock
Fitted
7871 0x1EBF RO
Value
Real Time Clock Fitted
0Not Fitted
1Fitted
Day Of The Week 7872 0x1EC0 R/W
Value
Day Of Week
1Monday
2Tuesday
3Wednesday
4Thursday
5Friday
6Saturday
7Sunday
Display Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
LED 1 Label 7660 0x1DEC R/W 5 ASCII characters, which can re read or written using
Modbus functions 16 or 23. Valid characters are 0 to
9, a to z, A to Z, plus ( ) -and _.
Defaults: 1 = PRI (Primary); 2 = SEC (Secondary);
3 = TUNE (Tuning); 4 = ALARM (Alarm)
LED 2 Label 7661 0x1DED R/W
LED 3 Label 7662 0x1DEE R/W
LED 4 Label 7663 0x1DEF R/W
LED 1 Usage 7664 0x1DF0 R/W
Value
LED 1 Usage
0Primary Control
1Secondary Control
2Tuning
3Any Alarm
4Alarm 1
5Alarm 2
6Alarm 3
7Alarm 4
8Alarm 5
9Event 1
10 Event 2
11 Event 3
12 Event 4
13 Event 5
14 Any Event
15 Manual Control
16 Profile Running
17 Profile Ended
LED 2 Usage 7665 0x1DF1 R/W
Value
LED 2 Usage
0Primary Control
1Secondary Control
2Tuning
3Any Alarm
4Alarm 1