3Field Upgrade Options

Options Modules and Functions

The available plug-in modules, options and accessories are shown in below:

Table 1. Options & Accessories

PART
NUMBER DESCRIPTION
BOARD
IDENTIFICATION
NUMBER
OPTION SLOT 1
51453391
-
517
Single Relay Output for option slot 1
51453391
-
502
Single SSR Driver Output for option slot 1
51453391
-
503
Triac Output for option slot 1
51453391
-
504
Linear mA / Voltage Output module for option slot 1
OPTION SLOT 2 or 3
51453391
-
518
Single Relay Output for option slot 2 or 3
51453391
-
510
Dual Relay Output for option slot 2 or 3
51453391
-
507
Single SSR Driver Output for option slot 2 or 3
51453391
-
519
Dual SSR Driver Output for option slot 2 or 3
51453391
-
508
Triac module Output for slot 2 or 3
51453391
-
509
Linear mA / Voltage Output for option slot 2 or 3
51453391
-
111
24VDC Transmitter Power Supply for option slot 2 or 3
OPTION SLOT A
51453391
-
513
Digital Input for option slot A
51453391
-
515
Basic Auxiliary Input for option slot A
51453391
-
512
RS485 Serial Communications for option slot A
51
453391
-
521
Ethernet Communications for option slot A
OPTION SLOT B
51453391
-
516
Full Auxiliary Input (inc digital input B) for option slot B
OPTION SLOT 4
51453391
-
520
4-Relay Output for option slot 4
ACCESSORIES
51453391
-
5
22
Blue Control PC Configuration Software & Lead
Note:

Modules can be either pre-installed at the time of manufacture, or retrofitted in the field.

CAUTION:

Plastic pegs prevent fitting of older non-reinforced single relay modules (Board

Identification Numbers 637/01 and 638/01). Fitting the older relay modules reduces

the isolation rating to Basic 240V Isolation and is therefore not recommended.

Remove this peg when fitting Dual Relay Modules.

Note:

All dual relay modules have reinforced isolation.