DCP200 Profile Controller & Recorder -Product Manual
51-52-25-150, Issue 1 April 2009 Specifications Page 173
17 Appendix 2 -Specifications

Universal Process Input

General Input Specifications

Input Sample Rate:
Ten samples per second.
Digital Input Filter
time constant
0.0 (OFF), 0.5 to 100.0 seconds in 0.5 second increments.
Input Resolution:
Always four times better than display resolution. 16 bit ADC.
Supply Voltage
Influence:
Negligible effect on readings within the specified supply voltage
tolerances.
Relative Humidity
Influence: Negligible effect on readings within the specified humidity tolerance.
Temperature
Stability: 0.01% of span/C change in ambient temperature.
Input Impedance:
V DC: 47KΩ
mA DC:
Other ranges: Greater than 10Mresistive
Isolation:
Isolated from all outputs (except SSR Drivers) at 240V AC
PV Offset:
Adjustable input span. +ve values are added to Process Variable, -ve
values are subtracted from Process Variable
PV Display:
Displays process variable up to 5% over and 5% under span.

Thermocouple Input

Thermocouple Types & Ranges
Sensor
Type Range in
C Range in
F
Sensor
Type Range in
C Range in
F
B100 to 1824°C 211 to 3315°F L0 to 762°C 32 to °F
C0 to 2315°C 32 to 4199°F N0 to 1399°C 32 to 2551°F
D0 to 2320°C 32 to 4208°F PtRh20%:
PtRh40%
0 to 1850°C 32 to 3362°F
E-240 to 1000°C -400 to 1832°F R0 to 1759°C 32 to 3198°F
J (default) -200 to 1200°C -328 to 2192°F S0 to 1762°C 32 to 3204°F
K-240 to 1373°C -400 to 2503°F T-240 to 400°C -400 to 752°F
Note:
Defaults to °F for USA units. Defaults to °C for non-USA units.
The Scale Range Upper Limit and Scale Range Lower Limit parameters, can be used to
restrict range. An optional decimal place can be displayed up to 999.9°C/F