DCP200 Profile Controller & Recorder -Product Manual
Page 112 Modbus Parameters 51-52-25-150, Issue 1 April 2009
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
10 Every 15 Minutes
11 Every 30 Minutes
Values To Display In
Trend View
9001 0x2329 R/W
Value
Trend View Data
0None (trend view off)
1Process variable only
2Process variable and setpoint
3Process variable maximum & minimum
since last sample
Profiler Control & Status Parameters
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
Profile Run/Hold
Signal
8192 0x2000 R/W
Value
Profile Run/Hold Sig
nal Source
0Operator Key Press Only
1Digital input A
2Digital input B
Profile Abort Signal 8193 0x2001 R/W
Value
Profile Abort Signal Source
0Operator Key Press Only
1Digital input A
2Digital input B
Active Profiler
Number
8243 0x2033 R/W Currently selected profile number (1 to 64)
Active Segment
Number
8244 0x2034 RO Currently active segment (1 to 255)
Profiler Control
Commands
8245 0x2035 R/W
Value
Profiler Command
0Do nothing
1Run the currently selected profile
2Hold the currently running profile
3Abort the currently running profile
4Jump to the next segment
5Release the hold
6Exit profiler, return to controller mode
Note:
The Profiler Control Commands
must
be followed by a
Profiler Control Confirmation Action command.
Profiler Control
Confirmation Action
8257 0x2041 R/W
Value
Implement Profiler Command
0Do Not Implement Command
1Implement previous Profiler Command
Enable Edit While
Running
8262 0x2046 R/W
Valu
e
Editing Current Running Profile
0Editing current running profile forbidden
1Editing current running profile allowed
Profile Control In
Operation Mode
8260 0x2044 R/W
Value
Profile Control From Operation Mode
0Operation Mode profile control disabled
1Operation Mode profile control enabled
Profile Cycles Run 8247 0x2037 RO The Number of times the currently running profile has
cycled