DCP200 Profile Controller & Recorder -Product Manual
51-52-25-150, Issue 1 April 2009 Modbus Parameters Page 107
Parameter Name
Modbus Address
Access
Values
(Dec)
(Hex)
1Start Recording
Data Recorder
Fitted
7553 0x1D81 RO
Value
Data Recorder Fitted
0Not Fitted
1Recorder Fitted
Memory Remaining 7554 0x1D82 RO Memory unused remaining left, in bytes
Time Remaining 7555 0x1D83 RO Time remaining until memory is used up, in seconds
Recorder Trigger 7563 0x1D8B R/W
Value
Recorder Trigger
0Operator start/stop
1Recorder Menu start/stop
2
On Alarm (
see Alarm 1
-
5 trigger below
)
3Digital input A
4Digital input B
5During running of profiles
Record Process
Variable
7572 0x1D94 R/W
Value
Record Process Variable
0Do Not Record PV
1Record PV Value
Record Maximum
PV Between
Samples
7573 0x1D95 R/W
Value
Record Max PV Since Last Sample
0Do Not Record Maximum PV
1Record Maximum PV Between Samples
Record Minimum PV
Between Samples
7574 0x1D96 R/W
Value
Record Min PV Since Last Sample
0Do Not Record Minimum PV
1Record Minimum PV Between Samples
Record Actual
Setpoint
7575 0x1D97 R/W
Value
Record Actual Setpoint Value
0Do Not Record Setpoint
1Record Actual Setpoint
Record Primary
Power
7576 0x1D98 R/W
Value
Record Primary Power Value
0Do Not Record Primary Power
1Record Primary Power
Record Secondary
Power
7577 0x1D99 R/W
Value
Record Secondary Power Value
0Do Not Record Secondary Power
1Record Secondary Power
Record Alarm 1
Status
7578 0x1D9A R/W
Value
Record Change Of State For Alarm 1
0Do Not Record Alarm 1
1Record Alarm 1
Record Alarm 2
Status
7579 0x1D9B R/W
Value
Record Change Of State For Alarm 2
0Do Not Record Alarm 2
1Record Alarm 2
Record Alarm 3
Status
7580 0x1D9C R/W
Value
Record Change Of State For Alarm 3
0Do Not Record Alarm 3
1Record Alarm 3
Record Alarm 4
Status
7581 0x1D9D R/W
Value
Record Change Of State For Alarm 4
0Do Not Record Alarm 4
1Record Alarm 4