51-52-25-150, Issue 1 April 2009 Electrical Installation Page 31

Option Slot 2 Single SSR Driver Output Module

If option slot 2 is fitted with a single SSR driver output module, make connections as
illustrated. The solid-state relay driver is a 0-10V DC signal, load impedance must be no less
than 500 ohms. SSR driver outputs are not isolated from the signal input or other SSR driver
outputs.
Figure 20. Option Slot 2 Single SSR Driver Module

Option Slot 2 Dual SSR Driver Output Module

If option slot 2 is fitted with a dual SSR driver output module, make connections as
illustrated. The solid-state relay drivers are a 0-10V DC signal, load impedance must be no
less than 500 ohms. SSR driver outputs are not isolated from the signal input or other SSR
driver outputs.
Figure 21. Option Slot 2 Dual SSR Driver Module

Option Slot 2 -Triac Output Module

If option slot 2 is fitted with a Triac output module, make connections as shown. This output
is rated at 0.01 to 1 amp @ 280V AC 50/60Hz. A snubber should be fitted across inductive
loads to ensure reliable switch off the Triac.
Figure 22. Option Slot 2 -Triac Module
22
23
_
24
+
23
24
22
23
-
OUTPUT 2A
-
OUTPUT 2B
24
+
COMMON