Wiring Connections
Wiring Connections
2.Make Phone Line Connections - For local or full line seizure proceed to the appropriate steps below.
Local Seizure
a.Connect the incoming phone line to either the
b.Connect the handset phone lines to either the RJ11 jack or terminals 4 (TIP) and 5 (RING).
Full Line Seizure: The control must be placed in series with the incoming phone line. Plugging the Direct Connect Cord directly into the RJ31X jack, allows the control to seize the phone line when an alarm occurs and normal phone line usage by the premises phones if the plug needs to be removed.
a. Cut the incoming RING and TIP phone lines (typically red and green, respectively) and connect them to RJ31X terminals 4 (red) and 5 (green).
b.Connect the premises end of the cut RING and TIP wires to RJ31X terminals 1 (grey) and 8 (brown) respectively.
c.Wire the flying leads of a Direct Connect Cord to the control’s phone terminals as shown in the diagram or plug into the
d. Plug the Direct Connect Cord into the RJ31X jack.
|
|
|
|
|
| INCOMING |
|
|
|
|
|
| PHONE LINE |
|
|
|
|
|
| RING |
|
|
|
|
|
| TIP |
| RED |
| 4 | 5 |
| GREEN |
|
|
| 3 |
| 6 | TO |
|
|
|
|
|
| |
|
|
| RJ31X |
| PREMISES PHONES | |
|
|
|
|
|
| RING |
|
|
| 2 |
| 7 | TIP |
| GREY |
| 1 |
| 8 | BROWN |
|
|
|
| DIRECT | ||
|
|
|
| CONNECT | ||
|
|
|
| CORD | ||
|
|
| OR |
|
|
|
GREEN | RED | BROWN | GREY |
|
|
|
|
|
|
|
|
| |
TIP | RING | TIP | RING |
|
| JACK |
} } |
|
|
| |||
INCOMING |
| TO |
|
|
| |
PHONE LINE | PREMISES |
|
|
| ||
|
| PHONES |
|
|
| |
|
|
|
|
|
| |
| Full Line Seizure Connections |
HARDWIRED ZONE: If the EOLR is not at the end of the loop, the zone will not be properly supervised, and the system may not respond to an open circuit on the zone.
3.Make Hardwired Zone Connections - Zone 1 is an EOLR supervised zone that supports both open circuit and closed circuit devices and has a response time of 350msec. Maximum zone resistance: 300 ohms, plus EOLR
Note: The hardwire zone cannot be used as a fire zone.
a.Connect sensors/contacts to the hardwired zone terminals 6 (+) and 7
b.Connect closed circuit devices in series in the high (+) side of the loop. The EOL resistor must be connected in series with the devices, following the last device.
c.Connect open circuit devices in parallel across the loop. The
4.Make External Sounder Connections - The control panel supports either a
a.Connect a piezo sounder to terminals 10 (+) and 11
UL
LOCAL SOUNDER DISABLE: The Master Keypad’s
Do not remove shorting jumper (the shunt) for UL installations.
5.Disable Local Sounder Option - If required the Master Keypad’s
a.Remove the shorting jumper (shunt) on the terminal board.
6.Make Powerline Carrier Device Connections - The control panel supports up to 8 Powerline Carrier Devices. If using these devices, they must be connected to the ADEMCO 1332X10 transformer, as shown in the SUMMARY OF CONNECTIONS diagram.
a.Connect the com/data/sync/ lines from the ADEMCO 1332X10 transformer to terminals 9, 13, and 14, respectively.
Note: If not using the supplied Ademco connection cable, you may need to reverse the black and yellow wire connections. Refer to the ✻80 Device Programming Menu Mode section for details on programming Powerline Carrier Devices.