Honeywell LYNXR Series Enhanced Zone Programming Mode, Zone number, Zone type, Report code

Models: LYNXR Series LYNXR-EN

1 72
Download 72 pages 18.53 Kb
Page 28
Image 28
Zone number

56 Enhanced Zone Programming Mode

While in Program mode, press 56 to enter Zone Programming Menu Mode. Refer to the zone assignment table for 56 on the separate programming form.

The following explains the 56 prompts in detail. The left two columns identify the prompts and list the available entries for each. The right-most column provides a further explanation of the entries.

Note: You may find it convenient to adjust the volume setting before entering the Programming Mode. This will allow you to clearly hear feedback announcements or system beeps.

 

 

 

 

 

Zone number

Enter the 2-digit zone number to be programmed and the Voice Descriptor

 

A

0I

 

01-41, 95, 96, 99 = Zone number

for the selected zone number will be announced, if it is programmed. Press

 

 

[] to advance.

 

 

 

[] = continue

 

 

 

Zone 01 = hardwire

 

 

 

 

 

 

00 = exit Zone Programming mode

 

 

 

 

 

 

Zones 02-25 = RF zones (only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Zones 26-41 = Button zones (only)

 

 

 

 

 

 

 

Zone 92 = Duress

 

 

 

 

 

 

 

Zones 95, 96, 99 = Panic zones

 

 

 

 

 

 

 

Pressing 00 exits mode, upon which the prompt “56” blinks, indicating the

 

 

 

 

 

 

mode is inactive. Press [] + any field number to go to that field.

 

 

 

 

 

 

 

 

 

 

 

 

Zone type

Each zone must be assigned to a zone type, which defines the way in

 

 

b

zt

 

00-24 = zone type

which the system responds to faults in that zone. Enter the 2-digit zone

 

 

 

type for this zone as follows:

 

 

 

 

[] = continue

 

 

 

 

00 = Not Used

08 = 24 Hr Aux

 

 

 

 

 

[#] = return to previous prompt

 

 

 

 

 

 

 

 

 

 

01 = Entry/Exit #1

09 = Fire without verify

 

 

 

 

 

 

 

 

 

 

 

Note: If 00 is accepted as a zone type, save the 00

02 = Entry/Exit #2

10 = Interior w/Delay

 

 

 

 

 

03 = Perimeter

20 = Arm–Stay

 

 

 

 

 

zone type and advance to the confirm delete

04 = Interior Follower

21 = Arm–Away

 

 

 

 

 

prompt (F).

05 = Trouble Day/Alarm Night

22 = Disarm

 

 

 

 

 

 

06 = 24 Hr Silent

23 = No Alarm Response

 

 

 

 

 

 

07 = 24 Hr Audible

24 = Silent Burglary

 

 

 

 

 

 

 

 

 

 

 

 

Report code

The report code consists of 2 hexadecimal digits, each in turn consisting of

 

 

C

rc

 

Enter the report code for this zone.

2 numerical digits. For example, for a report code of "3C", enter [0][3] for

 

 

 

"3" and [1][2] for "C".

 

 

 

 

[] = continue

 

 

 

 

If this is Zone 1, 95, 96 or 99, the system skips to the VOICE

 

 

 

 

 

[#] = return to previous prompt

 

 

 

 

 

DESCRIPTOR prompt (1C).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input type

Enter the input type for the transmitter assigned to this zone. Refer to the

 

 

d

i

 

3 =RF (supervised RF) – sends periodic

transmitter’s instructions for input types of each transmitter.

 

 

 

 

 

 

 

 

check-in signals, faults, restore and low

Note: Zones 2-25 should be assigned Input Type 3 or 4 . Zones 26-41

 

 

 

 

 

battery signals

 

 

 

 

 

should be assigned Input Type 5 only.

 

 

 

 

 

Note: RF type transmitters must remain within

 

 

 

 

 

 

 

 

 

 

 

 

range of the receiver, otherwise a

 

 

 

 

 

 

 

supervision failure signal will occur.

 

 

 

 

 

 

 

4 = UR (unsupervised RF) – sends same as

 

 

 

 

 

 

 

“RF” type, but control does not supervise

 

 

 

 

 

 

 

the check-in signals

 

 

 

 

 

 

 

5 = BR (button type) – sends only fault and low

 

 

 

 

 

 

 

battery signals; does not send restores or

 

 

 

 

 

 

 

check-in signals

 

 

 

 

 

 

 

Note UR and BR type transmitters may be carried

 

 

 

 

 

 

 

off premises (out of range without causing a

 

 

 

 

 

 

 

supervision failure.

 

 

 

 

 

 

 

[] = continue

 

 

 

 

 

 

 

[#] = return to previous prompt

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Loop number or Loop and Serial

This prompt can be used to enroll loop number and serial number via RF

 

 

E

 

 

 

l

 

number (if using RF Learning)

transmission or the loop number can be enrolled manually. If using the

 

 

 

RF Learning Mode, there is no need to manually enter a loop number.

 

 

 

1-4 = loop number for the zone of the

 

 

 

 

Proceed directly to RF Learning

 

 

 

 

 

 

transmitter being entered.

 

 

 

 

 

 

 

 

 

 

 

 

 

0 + [] = continue to DELETE ZONE

Notes: (1) BR type devices cannot be enrolled by using UR or RF type.

 

 

 

 

 

PARAMETERS CONFIRMATION

Likewise, UR or RF type devices cannot be enrolled by using a

 

 

 

 

 

prompt (F)

BR type device. There is a 52-second time-out for RF

 

 

 

 

 

[] = continue to the ENROLL MODE prompt

enrolling. At the end of the time-out, the system returns to

 

 

 

 

 

(1A) if not entered, or VOICE

the INPUT TYPE prompt (d). If enrolled, loop number and “L”

 

 

 

 

 

are displayed.

 

 

 

 

 

 

DESCRIPTOR prompt if already entered

 

 

 

 

 

 

(2) Once encrypted (high-security) devices have been enrolled they

 

 

 

 

 

[#] = return to previous prompt

 

 

 

 

 

must be activated. Refer to the device’s Installation

 

 

 

 

 

 

 

 

 

 

 

 

Instructions to activate the High-Security Mode.

 

 

 

 

 

 

 

 

–28–