Data Field Descriptions
Defaults (where applicable) are Indicated in Text.
The following pages list all data fields in this Control (in numerical order). Use the blank programming form to record the data for this installation. Note that both keypad LEDs flash while in Programming mode.
Note: Entering a number other than the one specified will give unpredictable results.
✻20 | Installer Code |
|
|
| The Installer Code is used to enter the | |
Enter 4 digits, |
|
|
| "Master Code" in the System Operation section for procedure. | ||
|
|
|
|
| ||
|
|
|
|
| ||
✻21 | Quick Arm Enable |
|
| If enabled, security code is not required to arm the system. The user | ||
0 | = do not allow quick arm |
|
| simply presses and holds down the AWAY or STAY key to arm. | ||
|
|
|
| |||
| 1 | = allow quick arm |
|
|
|
|
|
|
|
| |||
✻22 | Keypad Backlight Timeout |
| This option allows the choice of either always backlighting the keypad or | |||
0 | = no timeout; always backlight keys |
| turning the backlighting off after 10 seconds of keypad inactivity. | |||
|
|
| ||||
| 1 | = turn backlighting off after inactivity |
|
| ||
|
|
|
|
|
| |
✻23 | Forced Bypass |
|
|
| All zones bypassed by this function will be displayed after the bypass is | |
0 | = no forced bypass |
|
|
| initiated. | |
|
|
|
|
| ||
| 1 | = provide automatic bypass of all open (faulted) | Note: UL installations: must be 0 (no forced bypass) | |||
|
| zones |
|
|
| |
|
|
|
|
|
| |
|
|
|
|
| ||
✻24 | RF House ID Code |
|
| The House ID identifies receivers and wireless keypads. | ||
00 = disable all wireless keypad usage |
| If a 5827 Wireless Keypad or 5804BD/5804BDV Transmitter is to be | ||||
|
| used, a House ID Code MUST be entered, and the keypad should be set | ||||
|
|
|
| |||
|
|
|
| to the same ID. | ||
|
|
|
|
|
| |
✻25 | Powerline Carrier Device | Powerline Carrier Devices require a House ID. This field identifies this | ||||
0 = A 4 = E 8 = I | # + 12 = M | House ID to the Control. The Powerline Carrier Devices are | ||||
| programmed in field ✻80. | |||||
| 1 = B 5 = F 9 = J | # + 13 = N | ||||
|
| |||||
| 2 = C 6 = G # + 10 = K # + 14 = O |
| ||||
| 3 = D 7 = H # + 11 = L # + 15 = P |
| ||||
|
|
|
|
|
| |
✻26 | Chime by Zone |
|
|
| This option allows the installer to define the specific zones intended to | |
0 | = no (chimes on fault of any entry/exit or perimeter | chime when faulted while the system is in Chime mode. If enabled, these | ||||
| zones are defined in zone list 3 (see ✻81 Zone List Menu Mode). | |||||
|
| zone when Chime mode is activated |
| |||
|
|
|
| |||
| 1 | = yes (chimes on fault of those zones assigned to |
| |||
|
| Zone List 3 when Chime mode on) |
|
| ||
|
|
|
| |||
✻27 | Real Time Clock Display |
| Refer to the User’s Manual for setting the clock time and date. | |||
0 | = do not display the time |
|
|
| ||
|
|
|
| |||
| 1 | = display the time |
|
|
|
|
|
|
| ||||
✻29 | Daylight Savings Time Start/End Month | Enter # + 10 for 10, # + 11 for 11, and # + 12 for 12. | ||||
0, 0 = no daylight saving time used |
|
| ||||
|
|
| ||||
|
|
| ||||
|
|
| ||||
✻30 | Daylight Savings Time Start/End Week | Enter the appropriate start and end weekend of the month. | ||||
0 | = disable |
| 4 = fourth weekend |
| ||
|
|
| ||||
| 1 | = first weekend of month | 5 = last weekend |
| ||
| 2 | = second weekend |
| 6 = next to last |
| |
| 3 | = third weekend |
| 7 = 3rd from last |
| |
✻31 | Single Alarm Sounding Per Zone | UL installations: must be 0 (no limit) | ||||
(per armed period) |
|
|
| This field applies only to burglary zones (zone response types | ||
|
|
|
| and affects long range radio reporting but does not affect central station | ||
| 0 | = no limit on alarm sounding per zone |
| |||
|
| reporting. | ||||
| 1 | = limit alarm sounding to once per arming period for | ||||
|
| |||||
|
| a given zone |
|
|
| Note: This field applies only to the bell and does not affect keypad |
| LYNXR/LYNXR24 - Applies to Long Range Radio Output if “0” | |||||
| sounds. | |||||
| is selected in field ✻91 |
|
|
| ||
|
|
|
|
| ||
|
| |||||
| Radio is connected to the Trigger Single (Neg.) terminal #8. |
| ||||
|
|
|
| |||
✻32 | Fire Sounder Timeout |
| This Control complies with NFPA requirements for temporal pulse | |||
0 | = yes, fire sounder timeout after time programmed in | sounding of fire notification appliances. | ||||
| Temporal pulse sounding for a fire alarm consists of the following: | |||||
|
| field ✻33 |
|
|
| |
|
|
|
|
| 3 pulses – pause – 3 pulses – pause – 3 pulses. . . | |
| 1 | = no fire sounder timeout; continue sounding until | ||||
|
| |||||
|
| manually turned off |
|
|
| |
|
|
|
|
| ||
✻33 | Alarm Bell Timeout |
|
| This field determines whether the external sounder will shut off after | ||
0 | = No timeout | 2 = 8 min | 4 = 16 min | time allowed, or continue until manually turned off. | ||
| UL installations: must be set for a minimum of 4 min (option 1) | |||||
| 1 | = 4 min | 3 = 12 min |
| ||
|
|
| ||||
|
|
|
|
|
| |
✻34 | Exit Delay |
|
|
| The system will wait the time entered before sounding an alarm if the | |
| exit door is left open after the system has been armed. | |||||
|
| UL installations: must be set for a maximum of 60 seconds | ||||
|
|
|
|
|
| |
|
|
|
|
|
|
|