Item

Name

Description

 

 

 

11

Onboard Administrator module

Hot-pluggable enclosure management module. One

 

 

module is required to manage the components

 

 

installed in the enclosure. To provide redundant

 

 

enclosure management, you can install an optional

 

 

second module.

 

 

 

12

Onboard Administrator blank

A mandatory cover installed in any unused Onboard

 

 

Administrator bay

13

Interconnect blank

A mandatory insert installed in any unused

 

 

interconnect bay

 

 

 

14

Interconnect module (quantity and type as

Any of several components, such as pass-thrus or

 

ordered)

switches that enable communication between the

 

 

blade and the enclosure

 

 

 

15

Onboard Administrator tray

Hot-pluggable tray that houses up to two Onboard

 

 

Administrator modules and provides two enclosure link

 

 

connectors, the rear enclosure UID, LED, and switch.

 

 

 

16

HP BladeSystem Insight Display

A display that provides information about the health

 

 

and operation of the enclosure

17*

Power retention ties (single-phase enclosures

Tie straps that help prevent single-phase power cables

 

only)

from disconnecting from the power connectors

 

 

 

18*

Documentation CD

A CD containing detailed documentation on using the

 

 

enclosure

 

 

 

19*

Hard copy installation instructions for

The printed installation instructions

 

blades, options, and interconnects

 

20*

Installation checklist

A checklist to guide you through installation of the

 

 

enclosure and components

 

 

 

* Not shown

 

Rack requirementsThe enclosure is compatible with the following racks:

All HP 10000 and 10000G2 Series racks except the HP 10614 rack. NOTE: The system is optimized for 10000 Series racks.

Telco racks

Third-party rack cabinets that meet the following requirements: o Width: 48.3 cm (19 in)

o Depth:88.9 cm (35 in) maximum clearance between front and rear RETMA rails62.7 cm (24.7 in) minimum clearance for round-hole racks63.5 cm (25 in) minimum clearance for square-hole racks

oClearance—7.6 cm (3 in) minimum clearance between rear RETMA rails and rear rack door to accommodate system cabling

oClearance—4.5 cm (1.75 in) minimum clearance between rack face and inside of front rack door