vCircuit overloading – Power circuits and associated circuit breakers must provide sufficient power and overload protection. To prevent possible damage to the unit, isolate its power source from large switching loads (such as air conditioning motors, elevator motors, and factory loads).

vPower failures – If a total power failure occurs, the unit automatically performs a power-up recovery sequence without operator intervention after power is restored.

Table 20. DS4700 Express ac power requirements

 

Low Range

High Range

 

 

 

Nominal Voltage

90 to 136 VAC

198 to 264 VAC

 

 

 

Frequency (Hertz)

50 to 60 Hz

50 to 60 Hz

 

 

 

Idle Current

3.86 Aa

2.05 Ab

 

 

 

Maximum Operating Current

4 A/4.54 Aa c

2.12 A/2.41 Ab c

 

 

 

Maximum Surge Current

5.04 Aa

2.67 Ab

 

 

 

a.Typical voltage: 115 V ac, 60 Hz, assumes 72% power-supply efficiency and 0.99 power factor

b.Typical voltage: 230 V ac, 60 Hz, assumes 72% power-supply efficiency and 0.99 power factor

c.The higher number in this range applies when all of the drives are placed in Selfseek mode.

Table 21. DS4700 Express dc power requirements

 

Requirement

 

 

 

Operating Voltage

-42

V to -60 V

 

 

 

Nominal Voltage

-48

V

 

 

Idle Current

11.8 A

 

 

Maximum Operating Current

15.8 A

 

 

Maximum Surge Current

16 A

 

 

 

Power and site wiring requirements for models with ac power supply and fan units

The storage subsystem uses wide-ranging redundant power supplies that automatically accommodate voltages to the ac power source. The ac power supplies operate within the ranges specified in Table 20. The ac power supplies meet standard voltage requirements for both domestic (inside USA) and international (outside USA) operation. They use standard industrial wiring with line-to-neutral or line-to-line power connections.

The agency ratings for the DS4700 Express Storage Subsystem (ac models) are 6 amps at 100 VAC and 2.5 amps at 240 VAC. These are the overall maximum operating currents for the DS4700 Express Storage Subsystem with ac power supply and fan unit CRUs.

AC power recovery: After a total ac power failure, after normal power is restored, the storage subsystem performs power-up recovery procedures automatically without operator intervention.

Power cords and receptacles: The storage subsystem ships with two jumper cords used to connect to the rack PDU. You must purchase the power cords that

Chapter 1. Introduction 27