Attention: Turning off and turning on power without waiting for the storage subsystem disk drives to spin down can damage the drives and might cause data loss. Always let at least 70 seconds elapse from when you turn off the power until you turn on the power again.

Power-off overview

Review the following information before you continue with the power-off procedure below.

Turn off the power to each device based on the following shutdown sequence:

1.Turn off power to the host before the storage subsystem. If the host must stay powered on to support an existing network, see the operating system documentation for information about disconnecting the storage subsystem logical drives from the host before the storage subsystem is powered off.

2.Turn off power to the storage subsystem before you turn off power to the storage expansion enclosures. Turn off both power supply switches on the back of the storage subsystem.

3.(DS4700 Express dc models only) Turn off power to attached disconnect devices.

4.Turn off power to other supporting devices (for example, management stations, fibre-channel switches, or Ethernet switches).

Note: You do not need to perform this step if you are servicing only the storage subsystem.

Use the following procedure to turn off power to one or more storage subsystems for a planned shutdown. To turn off power for an unplanned shutdown, see “Restoring power after an unexpected shutdown” on page 137.

Before proceeding, use the Storage Manager client to determine the status of the system components and special instructions. The operating system software might require you to perform other procedures before you turn off the power.

1.Stop all I/O activity to each storage subsystem.

2.Remove the front cover from the storage subsystem, if applicable.

3.Determine the status of all storage subsystems and components in the configuration by completing the following steps:

a.Check all LEDs on each component in the storage expansion enclosures. Ensure that all the LEDs show normal status.

b.Check all LEDs on each component in the storage subsystem. Ensure that all the LEDs show normal status.

c.Open the Subsystem Management window for the configuration and display the Physical View for the configuration.

d.Review the status of the configuration components shown in the Subsystem Management window by selecting the appropriate component button for each storage subsystem.

The status for each component will be either Optimal or Needs Attention.

4.Are the LEDs indicating normal operation, and is the status Optimal on all configuration components?

v Yes - Go to step 6 on page 136. v No - Go to step 5 on page 136.