CAUTION:

To reduce the risk of electric shock or energy hazards:

vThis equipment must be installed by trained service personnel in a restricted-access location, as defined by the NEC and IEC 60950-1, First Edition, The Standard for Safety of Information Technology Equipment.

vConnect the equipment to a reliably grounded safety extra low voltage (SELV) source. An SELV source is a secondary circuit that is designed so that normal and single fault conditions do not cause the voltages to exceed a safe level (60 V direct current).

vThe branch circuit overcurrent protection must be rated 20 A.

vUse 12 American Wire Gauge (AWG) or 2.5 mm2 copper conductor only, not exceeding 4.5 meters in length.

vIncorporate a readily available approved and rated disconnect device in the field wiring.

CAUTION:

This unit has more than one power source. To remove all power from the unit, all dc MAINS must be disconnected.

CAUTION:

There is current to the power supply and fan units even though the power supply switch is in the OFF position. Use a disconnect device to shut power off before unplugging the dc power jumper cable from the dc power supply connectors.

There are two ways to cable the dc power supply and fan units:

vSingle-level redundant dc cabling

vDual-level redundant dc cabling

Single-level redundant dc cabling

In a single-level redundant dc cabling scheme, the DS4700 Express NEBS models are connected to the dc power source using the two dc power cords that are shipped. Only one dc power connector in each of the dc power supply and fan units is connected to a dc power source. The other dc power connector in each dc power supply and fan unit is left open. The dc power connectors A1 (5) are connected to the left dc power source (1) while dc power connectors B1 (6) are connected to the right dc power source (2). This cabling scheme protects against any single failure such as failed dc source, dc power supply, or dc cable. Figure 92 on page 113 illustrates single-level redundant cabling.

112IBM System Storage DS4700 Express Storage Subsystem: Installation, User’s and Maintenance Guide