Router Environmental Tolerances

Clearance Requirements for Airflow and Hardware Maintenance

When planning the installation site, you need to allow sufficient clearance around the rack (see Figure 17):

For the cooling system to function properly, the airflow around the chassis must be unrestricted. Allowing at least 6 in. (15.2 cm) of clearance between each side of the chassis and adjacent racks or equipment is recommended, particularly for routers in which air flows from side to side through the chassis. Figure 10 depicts the airflow in the M5 and M10 routers.

For service personnel to remove and install hardware components, there must be adequate space at the front and back of the router. Allow at least 24 in. (61 cm) in front of the router and 19 in. (48.3 cm) behind it.

Figure 17: Chassis Dimensions and Clearance Requirements

 

 

 

 

 

 

 

 

 

 

 

 

 

24" (61 cm)

 

 

 

 

 

 

 

 

 

 

19" (48.3 cm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6" (15.2 cm)

 

 

 

 

 

 

 

 

 

 

 

Clearance required

 

 

 

 

 

 

 

 

 

 

 

Clearance required

 

 

 

 

 

 

 

 

 

 

 

 

for maintenance

 

 

 

for airflow

 

 

 

 

 

 

 

 

 

for maintenance

 

 

 

 

 

 

 

 

 

 

 

 

 

Front of chassis

 

 

 

17.5"

 

 

 

 

44.5 cm

24"

19"

Rear of chassis

(61 cm)

 

(48.3 cm)

 

 

 

 

6" (15.2 cm)

Mounting ear

for airflow

1303

Router Environmental Tolerances

Table 8 specifies the environmental conditions required for normal router operation. In addition, the site should be as dust-free as possible. Dust can clog air intake vents, reducing cooling system efficiency. Check the vents frequently, cleaning them as necessary. For more information, see “Maintain Hardware Components” on page 75.

Table 8: Router Environmental Tolerances

Description

Tolerance

 

 

Altitude

No performance degradation to 10,000 ft (3048 m)

 

 

Relative humidity

Normal operation ensured in relative humidity range of 5% to

 

90%, noncondensing

 

 