TROUBLESHOOTING AND REPAIR

F-5

TROUBLESHOOTING GUIDE - Observe Safety Guidelines detailed in the beginning of this manual.

PROBLEMS

POSSIBLE AREAS OF

RECOMMENDED

(SYMPTOMS)

MISADJUSTMENTS(S)

COURSE OF ACTION

 

 

 

 

OUTPUT PROBLEMS

 

Return to

Return to Section TOC

Return to Section TOC

Return

Return to Master TOC

Return to Master TOC

No weld output and no auxiliary out- 1. The generator brushes may be

put - engine runs normally.worn or faulty. See the Main- tenance section of this manual or contact your local Lincoln Electric Authorized Field Ser- vice Facility.

1.Perform the Rotor and Flashing Voltage Test.

2.The field capacitor (C1) or bridge (D1) may be faulty. Test or replace.

3.Test the rheostat (R1). Normal resistance is 3.3 ohms.

4.The rotor may be faulty. Perform the Rotor Resistance Test.

Return to Section TOC

Return to Master TOC

1.Perform the Rotor and Flashing Voltage Test.CAUTION

If for any reason you do not understand the test procedures or are unable to perform the tests/repairs safely, contact the Lincoln Electric Service Department for technical troubleshooting assistance before you proceed. Call 1-888-935-3877.