3. Make sure lead 5 (white) is grounded to the machine frame (zero ohms).
4. Check for an open or grounded auxiliary winding in the stator, 6 to 3. See the Wiring Diagram.
CAUTION
If for any reason you do not understand the test procedures or are unable to perform the tests/repairs safely, contact the Lincoln Electric Service Department for technical troubleshooting assistance before you proceed. Call 1-888-935-3877.
POWERARC® 5500

Return to Section TOC

Return to Section TOC

Return to Section TOC

Return to Section TOC

Return to Master TOC

Return to Master TOC

Return to Master TOC

Return to Master TOC

F-7

TROUBLESHOOTING AND REPAIR

F-7

TROUBLESHOOTING GUIDE - Observe Safety Guidelines detailed in the beginning of this manual.

PROBLEMS

 

POSSIBLE AREAS OF

 

 

RECOMMENDED

(SYMPTOMS)

 

MISADJUSTMENTS(S)

 

 

COURSE OF ACTION

 

 

 

 

 

 

 

 

 

 

OUTPUT PROBLEMS

 

 

 

 

 

 

 

 

 

 

No auxiliary power - welding output

1.

Check circuit breakers CB1 and

1.

Check the auxiliary power re -

is normal - engine runs normally.

 

CB2. Reset if tripped.

 

ceptacles and associated wires

 

 

2.

Make sure that the control rheo-

 

for loose or faulty connections.

 

 

 

 

 

 

 

 

stat (R1) is set at “GENERATOR”

2.

Check the continuity (zero ohms)

 

 

 

(maximum).

 

of leads 3, 3A, 3B; 6, 6A, 6B, 6C;

 

 

3.

Check for loose or faulty plug at

 

and 5, 5A, 5B from the recepta-

 

 

 

cles to the stator windings. See

 

 

 

power receptacle.

 

 

 

 

 

the Wiring Diagram.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 