
Return to Section TOC
Section TOC
Return to Master TOC
Master TOC
TROUBLESHOOTING AND REPAIR |
CONTROL RELAY TEST (continued)
FIGURE F.1 – CONTROL RELAY TEST POINTS.
NORMALLY
CLOSED
NORMALLY
OPEN
COMMON
–+
24 VDC
Return to
Return to Master TOC
Return to Master TOC
TEST PROCEDURE
1.Remove the control relay from the control box per the Control Relay Replacement procedure.
2.Connect a 24 VDC supply to terminals A and B on the control relay. See Figure F.1. Do not energize the power supply at this time.
3.Connect a multimeter across the first set of terminals shown in the table below.
TABLE F.1 – CONTROL
RELAY CONTACT POSITIONS.
| Terminals | Terminals |
| A&B | A&B |
Terminals | Energized | |
|
|
|
Open | Closed | |
Closed | Open | |
Open | Closed | |
Closed | Open | |
Open | Closed | |
Closed | Open | |
|
|
|
4.Measure resistance across the contacts. A resistance of less than one Ohm indicates that the contacts are closed. An infinite resistance indicates that the contacts are open. Energize the 24 VDC power supply and measure the resistance again. Compare to the values given in the table for a good relay. If the readings do not match the table, the relay is faulty and should be replaced.
5.
6.Install the control relay per the Control Relay Replacement procedure.