4.8.3 Device Setting and Configuration
Make sure that the Coordinator is configured (using web access) to the settings below.
TCP Connection = any value from 1 to 5
Port number = 2000 (other values may be acceptable as long as Mail Notifier is setup
with the same Port number).
Then on the Mail Notifier Alarm Editor:
1) Set the “IP address” (for example 192.168.1.200).
2) Specify “Socket Number” 2000.
3) Set the “Address/RS485 Unit” to the Device ID number for an End Device.
4) Set the “Reading Cmd” using general commands in the Table below.
5) Define the Alarm Configuration (High/Low, High value, or Low value).
Specify Email Interval. This determines how many seconds each subsequential
alarm notification will be sent.
Determine Monitor interval. This establishes the interval or time resolution in
seconds for which readings will be obtained from the device.
Desired Value to Monitor Reading Cmd string Actual Command String
(see Note 2)
Reading A zRdgA ERDB003
Reading B zRdgB ERDB003
Reading C zRdgC ERDB003
Reading D zRdgD ERDB003
Battery voltage (mV) zBatt EQPE003
Signal Level zSignal EQPE003
Sleep Interval zSleep EQPE003
Status (see Note 4) zAddress EQNF003
1. The End Devices are configured in Mail Notifier with symbolic commands
rather than actual device commands.
2. zRdgA with RS485 Device Unit # as 3, for example, is sent as ERDB003.
3. “Reading A” will be the first value returned for a device in response to a
command such as ERDB003.
4. “Status” can be used to detect an address conflict. The value should be
tested to be at value 32 if there is an address conflict.
45