Sensaphone®Model 1108 User’s Manual
122
Problem Cause Solution
Other Monitoring (continued):
3. The Model 1108 does not recognize
power failure.
4. The Model 1108 does not recognize
any alarm.
a) Batteries are either incorrectly installed
or drained.
b) Recognition time setting is too long.
a) Inputs for alar m are disabled.
b) Programmed Recognition Time is too
long.
To verify proper battery function, unplug the
unit and verify continued operation using bat-
teries only. If unit ceases to function, first try
reinstalling the batteries. If this is not suc-
cessful, replace the batteries.
Refer to Chapter 2, Section 2.4 for complete
instructions.
Reprogram Recognition Time. Set the
Recognition Time to the minimum required
before a valid alarm occurs. If possible, test
the condition by deliberately creating an alert
condition.
Refer to Chapter 5, Section 5.9.
Enable the inputs for alarm.
Refer to Chapter 5, Section 5.2.
Reprogram Recognition Time. Set the
Recognition Time to the minimum required for
a monitored condition to become a valid