Other Monitoring (continued):
Problem | Cause | Solution | |
3. The Model 1108 does not recognize | a) Batteries are either incorrectly installed | To verify proper battery function, unplug the | |
power failure. |
| or drained. | unit and verify continued operation using bat- |
|
|
| teries only. If unit ceases to function, first try |
|
|
| reinstalling the batteries. If this is not suc- |
|
|
| cessful, replace the batteries. |
|
|
| Refer to Chapter 2, Section 2.4 for complete |
|
|
| instructions. |
| b) | Recognition time setting is too long. | Reprogram Recognition Time. Set the |
|
|
| Recognition Time to the minimum required |
|
|
| before a valid alarm occurs. If possible, test |
|
|
| the condition by deliberately creating an alert |
|
|
| condition. |
|
|
| Refer to Chapter 5, Section 5.9. |
|
|
| |
4. The Model 1108 does not recognize | a) Inputs for alarm are disabled. | Enable the inputs for alarm. | |
any alarm. |
|
| Refer to Chapter 5, Section 5.2. |
| b) Programmed Recognition Time is too | Reprogram Recognition Time. Set the | |
|
| long. | Recognition Time to the minimum required for |
|
|
| a monitored condition to become a valid |