Other Monitoring (continued):

Problem

Cause

Solution

3. The Model 1108 does not recognize

a) Batteries are either incorrectly installed

To verify proper battery function, unplug the

power failure.

 

or drained.

unit and verify continued operation using bat-

 

 

 

teries only. If unit ceases to function, first try

 

 

 

reinstalling the batteries. If this is not suc-

 

 

 

cessful, replace the batteries.

 

 

 

Refer to Chapter 2, Section 2.4 for complete

 

 

 

instructions.

 

b)

Recognition time setting is too long.

Reprogram Recognition Time. Set the

 

 

 

Recognition Time to the minimum required

 

 

 

before a valid alarm occurs. If possible, test

 

 

 

the condition by deliberately creating an alert

 

 

 

condition.

 

 

 

Refer to Chapter 5, Section 5.9.

 

 

 

4. The Model 1108 does not recognize

a) Inputs for alarm are disabled.

Enable the inputs for alarm.

any alarm.

 

 

Refer to Chapter 5, Section 5.2.

 

b) Programmed Recognition Time is too

Reprogram Recognition Time. Set the

 

 

long.

Recognition Time to the minimum required for

 

 

 

a monitored condition to become a valid