Sensaphone® Model 1108 User’s Manual

IV. The Alarm Is Acknowledged

Variable Factors

 

 

• At any time after a valid alarm is

Local, On-site

determined, the alarm may be

Acknowledgment

acknowledged at the Model 1108’s

 

installation site, by pressing any key.

 

• When the Model 1108 dials out and the

 

call is answered via Touch-Tone

 

telephone, any alarm may be instantly

Touch-Tone

acknowledged by pressing “555.”

Acknowledgment:

• If the alarm message repeats for the

Fast Code 555

number of programmed Voice

 

Repetitions, and “555” has not been

 

entered, the Model 1108 will say:

 

“Indicate that you have received warning

 

message.”

 

The Model 1108 waits 10 seconds for the

Touch-Tone

Touch-Tone code “555” to be entered. If

Acknowledgment:

the code is entered within 10 seconds, it

Normal Code 555

responds:

 

Warning message received by telephone

 

number...(the dialed phone number).”

 

The alarm is considered acknowledged

 

and the dialout concludes.

Tone or Pulse

 

• If the Model 1108 does not receive the

Callback

Touch-Tone code within 10 seconds, it

Acknowledgment:

recites the following and then hangs up:

Within Intercall

“Dial telephone number (gives the Unit ID

Time

 

Number) within...(the programmed Intercall

 

Time.)”

 

The recipient of this message must call

 

the Model 1108 back within the period

 

programmed for Intercall Time, in order

 

to acknowledge the alarm. If Local Voice

 

Mute is off, the unit will beep at the

 

installation site while waiting for this

 

call.

 

• Callback: The Model 1108 waits 10 rings

 

before answering to guard against

 

random acknowledgment. If an

 

 

 

96

Page 96
Image 96
Phonetics 1108 user manual Local, On-site