Appendix C: 1108 QUICK REFERENCE

Parameter

Description

Key Sequence*

Range

Default

Call Delay

Time delay until

[SET] or [WHAT IS]

Min: 00:00

00:30

 

first call is made

+ [CALL DELAY]

Max 60:00

(min:sec)

 

 

 

(min:sec)

 

 

 

 

 

 

Voice Reps

Number of times alarm

[SET] or [WHAT IS]

Min: 0 reps

3 reps

 

message is repeated

+ [VOICE REPS]

Max: 10 reps

 

 

over the phone

 

 

 

 

 

 

 

 

Intercall Time

Time delay between

[SET] or [WHAT IS] +

Min: 00:10

01:00

 

phone calls

[INTERCALL TIME]

Max: 60:00

(min:sec)

 

 

 

(min:sec)

 

 

 

 

 

 

Max Calls

Number of calls until unit

[SET] or [WHAT IS] +

Min: 0 calls

100 calls

 

self-acknowledges

[MAX CALLS]

Max: 255 calls

 

 

 

 

 

 

Temp Limits

High and low temperature

[SET] or [WHAT IS] +

Min: -20°F/-30°C

Low: 10°F

 

alarm limits

[TEMP LIMITS] +

Max: 150°F/65°C

High:

 

 

[input #]

 

100°F

 

 

 

 

 

Calibrate

Temperature Correction

[SET] or [WHAT IS] +

Min: -10°

 

factor

[CALIBRATE] +

Max: 10°

 

 

 

[input #]

 

 

 

 

 

 

 

Recognition

Length of time a

[SET] or [WHAT IS]

Min: 00:00

00:03

Time:

fault condition must exist

+ [RECOGNITION

Max: 272:00

(min:sec)

inputs 1–8

to trip an alarm

TIME] + [input#]

(min:sec)

 

 

 

 

 

 

Recognition

Length of time the

[SET] or [WHAT IS]

Min: 00:00

05:00

Time: Power

power must be off

+[RECOGNITION

Max: 272:00

(min:sec)

Failure

to trip an alarm

TIME]+[POWER]

(min:sec)

 

 

 

 

 

 

Recognition

Length of time the

[SET] or [WHAT IS]

Min: 00:00

00:08

Time: High

sound must be high

+[RECOGNITION

Max: 272:00

(min:sec)

Sound Level

to trip an alarm

TIME] + [SOUND]

(min:sec)

 

 

 

 

 

 

Clock

Real time clock

[SET] or [WHAT IS] +

Min:

12:00 AM

 

 

[CLOCK] + [time] +

Max:

 

 

 

[AM] or [PM]

 

 

 

 

 

 

 

High Sound

Microphone sensitivity

[SET] or [WHAT IS] +

Min: 1 unit

32 units

Level Alarm

for high sound

[CALIBRATE] +

Max: 255 units

 

Sensitivity

level alarm

[SOUND]

 

 

 

 

 

 

 

Listen Time

Length of listen-in time

[SET] or [WHAT IS] +

Min: 0 sec

00:15

 

during call-in status report

[LISTEN TIME]

Max: 255 sec

(min:sec)

 

 

 

 

 

Rings Until

Number of rings until unit

[SET] or [WHAT IS] +

Min: 1 ring

4 rings

Answer

answers an incoming call

[RING]

Max: 15 rings

 

 

 

 

 

 

* press [ENTER] after all Key Sequences starting with [SET]

125

Page 125
Image 125
Phonetics user manual Appendix C 1108 Quick Reference, Parameter Description Key Sequence Range Default