125

Parameter Description Key Sequence* Range Default

Call Delay Time delay until
first call is made
[SET] or [WHAT IS]
+ [CALLDELAY]
Min:00:00
Max 60:00
(min:sec)
00:30
(min:sec)
Voice Reps Number of times alarm
message is repeated
over the phone
[SET] or [WHAT IS]
+ [VOICEREPS]
Min:0 reps
Max:10 reps
3 reps
Intercall Time Time delay between
phone calls
[SET] or [WHAT IS] +
[INTERCALLTIME]
Min:00:10
Max:60:00
(min:sec)
01:00
(min:sec)
Max Calls Number of calls until unit
self-acknowledges
[SET] or [WHAT IS] +
[MAXCALLS]
Min:0 calls
Max:255 calls
100 calls
Temp Limits High and low temperature
alarm limits
[SET] or [WHAT IS] +
[TEMP LIMITS] +
[input #]
Min:-20°F/-30°C
Max:150°F/65°C
Low:10°F
High:
100°F
Calibrate Temperature Correction
factor
[SET] or [WHAT IS] +
[CALIBRATE] +
[input #]
Min:-10°
Max:10°
Recognition
Time:
inputs 1–8
Length of time a
fault condition must exist
to trip an alarm
[SET] or [WHAT IS]
+ [RECOGNITION
TIME] + [input#]
Min:00:00
Max:272:00
(min:sec)
00:03
(min:sec)
Recognition
Time:Power
Failure
Length of time the
power must be off
to trip an alarm
[SET] or [WHAT IS]
+[RECOGNITION
TIME]+[POWER]
Min:00:00
Max:272:00
(min:sec)
05:00
(min:sec)
Recognition
Time:High
Sound Level
Length of time the
sound must be high
to trip an alarm
[SET] or [WHAT IS]
+[RECOGNITION
TIME] + [SOUND]
Min:00:00
Max:272:00
(min:sec)
00:08
(min:sec)
Clock Real time clock [SET] or [WHAT IS] +
[CLOCK] + [time] +
[AM] or [PM]
Min:
Max:
12:00 AM
High Sound
Level Alarm
Sensitivity
Microphone sensitivity
for high sound
level alarm
[SET] or [WHAT IS] +
[CALIBRATE] +
[SOUND]
Min:1 unit
Max:255 units
32 units
Listen Time Length of listen-in time
during call-in status report
[SET] or [WHAT IS] +
[LISTEN TIME]
Min:0 sec
Max:255 sec
00:15
(min:sec)
Rings Until
Answer
Number of rings until unit
answers an incoming call
[SET] or [WHAT IS] +
[RING]
Min:1 ring
Max:15 rings
4 rings
Appendix C: 1108 QUICK REFERENCE

* press [ENTER] after all Key Sequences starting with [SET]