Sensaphone® Model 1108 User’s Manual

affecting that input. If an input is disabled, the word “Off” immediately follows the number recited for that input.

For example, input 3 is configured as a normally open, dry contact input. During the Status Report:

If disabled, the Model 1108 recites: “Number 3—Off—OK,”for input 3.

If enabled, the Model 1108 recites: “Number 3—OK,”for input 3.

In another example, input 2 is configured as a temperature input. The current temperature is 76 degrees. During a Status Report:

If disabled, the Model 1108 recites: “Number 2—Off—76degrees—OK.”

If enabled, the Model 1108 recites: “Number 2—76degrees—OK.”

5.3Input Recognition Time

The Input Recognition Time is the length of time an alert condition must be present before a valid alarm exists and dial-out is activated. This time period is programmable, from 0 minutes, 0 seconds (for immediate response) up to a period of 272 minutes, 0 seconds. If an alert condition begins and then clears within the established Recognition Time, no dial-out will occur. When an alert condition continues beyond the programmed Recognition Time, the Model 1108 initiates dial-out. The default setting for Input Recognition Time is 0 minutes, 3 seconds.

5.3.1Programming Input Recognition Time

1.Press SET.

2.Press RECOGNITION TIME.

70

Page 70
Image 70
Phonetics 1108 user manual Programming Input Recognition Time