INSTALLATION
INSTALLATION
VENTING ARRANGEMENTS
ALLOWABLE HORIZONTAL TERMINATIONS
The diagram shows all allowable combinations of vertical runs with horizontal terminations, one 90o elbow (two 45o elbows equal one 90o elbow).
Note: Must use optional rigid pipe adapter (Part #
Horizontal (Feet)
Vertical Height (Feet)
14
12
10
8
6
4
2
0
0 | 2 | 4 | 6 |
Vent Restrictor
on Set 2
Vent Restrictor
on Set 1
8 | 10 | 12 | 14 | 16 | 18 | 20 |
Vent Restrictor
Factory Set
Refer to "Vent Restrictor Position" section for details on how to change the vent restrictor to Set 1 or Set 2 if required. A vent guard maybe required as per local codes, refer to "Exterior Vent Termination Requirements" section for details.
Note: Regency® Direct Vent System (Flex) is only approved for horizontal terminations.
•Maintain clearances to combustibles as listed in "Clearances" section
•Horizontal vent must be supported every 3 feet.
•Firestops are required at each floor level and whenever passing through a wall.
•A wall thimble is required for all horizontal terminations.