INSTALLATION
For 0 to 4500 feet altitude |
| |
Front Burner Orifice: | #44 | |
Back Burner Orifice: | #35 | |
|
| |
Max. Input Rating | 45,000 Btu/h | |
Min. Input Rating | 13,000 Btu/h | |
|
| |
Supply Pressure | min.5.0" w.c. | |
|
|
|
Manifold Pressure |
|
|
(High) | 3.5"+/- 0.3"w.c. |
Log Set: Ceramic fibre,
8 per set + ember bed.
Vent System: Simpson
Vent System, Regency® Flex Kit, Selkirk
Conversion Kit# |
| |
For 0 to 4500 feet altitude |
| |
Front Burner Orifice: | #55 | |
Back Burner Orifice: | #53 | |
|
| |
Max. Input Rating | 43,000 Btu/h | |
Min. Input Rating | 12,000 Btu/h | |
|
| |
Supply Pressure | min.12.0" w.c. | |
|
|
|
Manifold Pressure |
|
|
(High) | 10"+/- 0.5" w.c. |
Log Set: Ceramic fibre,
8 per set + ember bed.
Vent System: Simpson
Vent System, Regency® Flex Kit, Selkirk
GAS LINE
INSTALLATION
The gas line can be brought through the bottom right of the appliance. The gas valve is situated on the bottom of the unit.
The gas line connection may be made of rigid pipe, copper pipe or an approved flex connector. (If you are using rigid pipe, ensure that the valve can be removed for servicing.) Since some municipalities have additional local codes it is always best to consult with your local authorities and the CAN/CGA B149 installation code.
For USAinstallations follow local codes and/or the current National Fuel Gas Code, ANSI Z223.1.
When using copper or flex connectors use only approved fittings. Always provide a union so that gas lines can be easily disconnected for servicing. Flare nuts for copper lines and flex connectors are usually considered to meet this requirement.
IMPORTANT: Always check for gas leaks with a soap and water solution or gas leak detector. Do not use open flame for leak testing.
PILOT ADJUSTMENT
Periodically check the pilot flames. Correct flame pattern has three strong blue flames: 1 flowing around the thermopile, 1 around the thermocouple and 1 flowing across the burner (it does not have to be touching the burner).
Note: If you have an incorrect flame pattern, contact your Regency® dealer for further instructions.
Incorrect flame pattern will have small, probably yellow flames, not coming into proper contact with the rear burner or thermopile or thermocouple.
INSTALLATION
HIGH ELEVATION
This unit is approved in Canada for altitude 0 to 4500 ft. (CAN1