3.6Environment

Network

Management Card

User Manual

list. Connection is made with the server and the date and time are set after clicking on the “Save” button. Time is updated every hour.

The card uses the NTP protocol (UDP 123 port) and the firewall must be set accordingly, no error message is generated if the time server contact fails

Daylight Saving Time: Enables corrections due to summer / winter time changes, this option must be supported by the NTP server.

Note 1:

Time drift is related to card electronics. It may be up to a maximum of +/- 2min/month.

3.6Environment

The environment sensor is an option that enables temperature and humidity to be measured, and indication of the position of two external contacts. It is connected with a standard network cable to the Card Settings port of the Network Management Card.

On startup, the card automatically detects sensor presence. The main menu then displays an additional section “Environment” with the following elements:

Status

Configuration

Log

Note 1 This function is only accessible with the DA version software (or superior) for the card. This software can be downloaded on the www.apc.com site, from the download section.

Note 2: To switch the serial port to the configuration mode, just disconnect the sensor cable and reinitialise the card by pressing “Reset”. The reverse operation must be performed to manage the environment sensor once again.

3.6.1 Characteristics

Temperature measurement from 0 to 70 °C with +/- 1° C accuracy

Humidity measurement from 0 to 100 % with +/- 6 % accuracy

Min. / max. time-stamped function for temperature and humidity

Choice of displaying temperature in Celsius or Fahrenheit

High and low thresholds, hysteresis and offset adjustment via Web interface

Possibility of notification of status changes by e-mail, SMS or SNMP trap

Position detection of 2 dry contacts (maximum sensor/contact distance: 20m)

Network Management Card – User Manual

34003676EN/HA

Page 54/81