3.2.9 Shutdown parameters

Network

Management Card

User Manual

3.2.9 Shutdown parameters

Click on the “Shutdown parameters” section in the menu to see the list of parameters.

Important note:

For installations that do not use Network Shutdown Module (backup units, routers and other internetworking equipment, automated systems, etc.) or in the event of long backup periods, the card will send a command to the UPS (dependant of the UPS settings and UPS type) to shut off end of the programmed Shutdown After time. To prevent this, the Shutdown After box must be not selected (default)

This page enables viewing and configuration of UPS operation parameters in battery mode and for power restoration.

When you tick the Show advanced parameters option, extra parameters are displayed. These parameters enable, in particular, adjustment of certain thresholds related to the percentage of remaining battery charge level.

The Output column enables each output to be named (maximum 30 characters).

Note

For the output

Shutdown after is the operating time in minutes left for users after a switch to backup before starting the shutdown sequences of the UPS and its equipment (from 0 to 1092).

If remaining time under (from 0 to 9999 seconds) and If Capacity under (from 0 to 100%) are two extra conditions for remaining backup time and battery level that can trigger shutdown sequences before the “Shutdown after” period runs out

Shutdown duration is the time required for complete shutdown of systems when a switch to backup time is long enough to trigger the shutdown sequences. It is calculated automatically at the maximum of Shutdown duration of subscribed clients but can be modified in the Advanced mode

Restart after is the minimum shutdown time before restarting the UPS after a shutdown sequence. It is thus possible to limit repeated restarts that may be due to several successive utility failures.

If the Battery is charged for and If Capacity exceeds are two extra conditions for minimum battery level and maximum recharge time to be reached before restarting the UPS after utility restoration

Security: The administrator has to click on Save and enter his login/password to save any modifications. The

default login and password are: MGEUPS