◗Shutdown after : is the time available to the user from the Power failure until the launch of the shutoff sequence of the UPS. This parameter is optionnal.
Many actions are available on this page :
◗Remove : Depending on the kind of application, the selected ones will definitively disappear from the table as SNMP applications, or they will disappear and automatically
◗Utility failure Test : Two alarms 'Utility failure' and 'Utility restored' spaced of 60 seconds will be sent to the applications selected, making sure that the applications can be reached over the network.
◗Shutdown Test : This test simulates a UPS on battery operation, it sends alarms to the selected applications. It enables an easy check to see if the server protection works correctly.- No intervention on the UPS is required.
-Simulated alarms will be processed by the applications selected only.
-Warning :This test will generate a REAL shutdown sequence of servers on which Network Shutdown Module is running.
Add NMS allows to add a SNMP trap receiver as a Network Management System.
Modify NMS allows to modify a SNMP trap receiver.
Both buttons makes appear a new window where it is possible to enter the Application name, the Hostname or IP Address, the Trap community and the severity.