Network

Management Card

User Manual

4.2The different server and UPS shutdown sequences

4.2.1 Extended power outage, shutdown initiated by the Shutdown Timer

During battery backup time, the Shutdown Timer of the Network Management Card is reached: after a user-

defined backup time period, the shutdown of all servers is initiated, followed by the UPS shutdown (depending

on its configuration). The UPS restarts when utility power is restored (depending on its configuration).

Shutdown Duration: Maximum value of shutdown times of the Network Shutdown Modules subscribed to the card and depending on the main UPS output. This value is updated each time a client subscribes/

unsubscribes.

Note: During battery operation, these values are not updated.

Shuts down after the ShutDown Timer + Shutdown Duration after having stopped the servers Restarts when utility power is restored (possibility of programming a restart delay)

Utility ON

OFF

ON

Trap 17

ShutdownTim

Trap,11, Trap 29

er

 

Trap 31

 

 

Trap 18

Shutdown

Duration

Trap 32

NSM

Shutdown

Reboot

UPS output

OFF

Network Management Card – User Manual

34003676EN/HA

Page 62/81

Page 62
Image 62
Schneider Electric 66846, 66074 user manual Different server and UPS shutdown sequences