7 Maintenance

Network

Management Card

User Manual

7 Maintenance

7.1Software upgrade

7.1.1 Card firmware upgrade using Mupgrade (Windows)

This feature is particularly useful to upgrade a large UPS installed base in one operation.

Read the relevant documentation available for download on the www.apc.com web site.

7.1.2 Card software upgrade via TFTP (UNIX and Windows)

Upgrading is also possible with TFTP command.

Generic command, with default value, is:

tftp -i @IP put nmc_fb.bin upgrade@MGEUPS@MGEUPS

Where:

-i indicates binary mode

@IP is the address of the NMC card nmc_fb.bin is the firmware name

Caution the last parameter upgrade@MGEUPS@MGEUPS, represent the default value of

upgrade@password@username. This parameter is build like an unique word, without any blank character inside.

password value defined in the acces control page username value defined in the acces control page

Check syntax depending of your operating system

7.1.3 Recovery tool software Msupgrade (Windows) via the serial link

Read the relevant documentation available for download on the www.apc.com web site.