Network
Management Card
User Manual
The high alarm cannot be reactivated while temperature remains above the High threshold – Hysteresis value.
The low alarm cannot be reactivated while temperature remains below Low threshold + hysteresis value.
Humidity
High threshold: if this value is exceeded, a notification is sent if enabled. Default value is 90%.
Low threshold: if this value is exceeded, a notification is sent if enabled. Default value is 5%. Hysteresis must be set to prevent multiple notifications if humidity fluctuates around a threshold. Default value is 5%. (Advanced parameters)
The high alarm cannot be reactivated while humidity remains above the High threshold – Hysteresis value. The low alarm cannot be reactivated while humidity remains below Low threshold + hysteresis value.
Input No 1 and Input No 2: enter an identifier corresponding to the acquired contact (e.g.: rack door, air conditioning, generator unit, etc.). Max. length is 28 characters.
If contact closed and if contact open: are the names associated to the two contact positions. (e.g.: "open" and "closed" for a door, "On" and "Off" for a generator).
Each status change triggers a notification if enabled.
Notification includes: Log, Notification by
System shutdown can be triggered for each notification if this option is enabled. If notification is disabled, the Shutdown option cannot be used. (Advanced parameters)
Security: the administrator has to click on Save and enter his login/password to save any modifications.
3.6.3.2 STS Environment Settings
Network Management Card – User Manual | 34003676EN/HA | Page 58/81 |