Network

Management Card

User Manual

1.7Technical data

1.7.1 Configuration

The user can configure the card with one of the following means:

Web browser

Local serial link

Telnet console

BOOTP/DHCP

Mupgrade

1.7.2 Administration

Up to 50 workstations protected

Up to 15 browsers connected at the same time

E-mail sending configurable according to UPS alarms and transmission of a periodical report

Measurement of temperature and humidity, adjustable thresholds, possibility of sending e-mails and shutting down the installation

Control of UPS on/off switching via the HTML interface

Adjustment and control Power via the HTML interface, sequential starting of the installation and optimisation of backup time by shutting down non-priority systems

Adjustment of date and time via NTP server - Daylight Saving Time management

Protection by encrypted password.

Protection by secured connection SSL and SSH

Saving of logs in the non-volatile memory

Automatic language detection according to browser configuration.

Languages available: English / French / Spanish / German / Italian

On-line help available for each page

Card firmware updated via the network

Card configuration deployment on your installed base through network utility (Mupgrade)

1.7.3 Network

Fast ETHERNET 10/100 Mbits compatibility with auto-negotiation on the RJ45 outlet

SNMP trap port modifiable (by default = 162)

1.7.4 MIB (Management Information Base)

MIB IETF UPS (RFC1628) for UPS

MIB MGE V1.7 AD, for UPS

MIB MGE V2.2 AA, for STS

1.7.5 Environment sensor

Temperature measurement from 0 to 70 °C with +/- 1° C accuracy

Measurement of humidity from 0 to 100 % with +/- 6 % accuracy

Min / max time-stamped function for temperature and humidity

Choice of temperature readings in Celsius or Fahrenheit

High and low thresholds, hysteresis and offset adjustable via Web interface

Network Management Card – User Manual

34003676EN/HA

Page 9/81

Page 9
Image 9
Schneider Electric 66074, 66846 user manual Technical data